Plan Review Notes
Plan Review Notes For Permit 08040226
Permit Number 08040226
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-21 14:51:442004 FBC W/2007 REVISIONS
 ADDITION AND DECK
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THERE ARE TWO STRUCTURES LOCATED ON THE SAME PARCEL.
 THERE WERE PLANS SUBMITTED FOR A SINGLE STORY BUILDING,
 A TWO STORY STRUCTURE AND A SITE WALL. THE TITLE BLOCK
 ON ALL THREE PLANS ONLY PROVIDE THE OWNER NAME AND
 ADDRESS. IN ORDER TO AVOID CONFUSION, PLEASE SPECIFY
 THE STRUCTURE TO WHICH THE PLANS APPLY IN THE TITLE
 BLOCKS. FBC 106.1* CITY AMENDMENTS.
  
 TWO STORY STRUCTURE
  
 1) ON SHEET A-2 THE SECOND FLOOR FLOOR PLAN SAYS TO SEE
 DETAIL C. THERE DOES NOT APPEAR TO BE A DETAIL C
 PROVIDED. PLEASE CLARIFY.
  
 2) ON SHEET D-1 THE 6 X 6 POSTS IN CONTACT WITH THE
 SOIL ARE NOT SPECIFIED AS BEING PRESSURE TREATED ON
 SHEET D-1.
  
 3) ON SHEET A-2 SECTION A AT THE DECK IS INDICATED ON
 THE SECOND FLOOR PLAN. HOWEVER, THERE DOES NOT APPEAR
 TO BE A SECTION A PROVIDED. PLEASE CLARIFY.
  
 4) SPECIFY HOW THE 2 X 10 FLOOR JOISTS ARE ATTACHED TO
 THE (3) 2 X 10S LOCATED ATOP THE 6 X 6 POSTS. FBC
 106.1.2* CITY AMENDMENTS.
  
 5) THE SECOND FLOOR PLAN ON A-2 SPECIFIES A 4 PLY 2 X
 10 IN ONE LOCATION AT THE 6 X 6 POSTS AND (3) IN THE
 OTHER. PLEASE CLARIFY.
  
 6) ON SHEET D-1 PART OF THE TEXT IS MISSING FROM THE
 NOTES AT THE LEFT SIDE OF THE PAGE.
  
 7) SUBMIT (2)TWO COPIES OF PRODUCT APPROVALS THAT
 HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD FOR THE PROJECT. FBC 106.3.3* CITY
 AMENDMENTS.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG WINDOWS
 AS REQUIRED BY DCA RULE 9B-72.
  
 ONE STORY STRUCTURE
  
 1) ON SHEET S-1 THE WALL SECTION SHOWS THE STUCCO
 FINISH EXTENDING BELOW GRADE. THIS DOES NOT COMPLY WITH
 SECTION 704 INSPECTION FOR TERMITES. IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM). PLEASE CORRECT.
  
 2) AT THE ADDITION, SHOW COMPLIANCE WITH R408.1
 VENTILATION.
 THE UNDER -FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT OR CELLAR) SHALL BE PROVIDED
 WITH VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR
 EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION
 OPENINGS SHALL NOT BE LESS THAN 1 SQUARE FOOT FOR EACH
 150 SQUARE FEET (0.67 M 2 FOR EACH 100 M 2 ) OF UNDER
 -FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING SHALL
 BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF SAID
 BUILDING.
 UNDER FLOOR
  
 3) AT THE ADDITION, SHOW COMPLIANCE WITH R408.3 ACCESS
 SHALL BE PROVIDED TO ALL UNDER -FLOOR SPACES. ACCESS
 OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF 18
 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS
 THROUGH A PERIMETER WALL SHALL BE 16 INCHES BY 24
 INCHES (407 MM BY 610 MM). WHEN ANY PORTION OF THE
 THROUGH WALL ACCESS IS BELOW GRADE, AN AREAWAY OF NOT
 LESS THAN 16 INCHES BY 24 INCHES (407 MM BY 610 MM)
 SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY SHALL BE
 BELOW THE THRESHOLD OF THE ACCESS OPENING. THROUGH WALL
 ACCESS OPENINGS SHALL NOT BE LOCATED UNDER A DOOR TO
 THE RESIDENCE. SEE M1305.1.4 FOR ACCESS REQUIREMENTS
 WHERE MECHANICAL EQUIPMENT IS LOCATED UNDER FLOORS.
  
 4) SUBMIT ENERGY CALCULATION FORMS SIGNED BY THE
 OWNER/AGENT AS REQUIRED BY FBC 13-600 FOR THE BATH ROOM
 ADDITION.
  
 5)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 6) SPECIFY THE ATTACHMENT OF THE NEW FOOTER AND WALLS
 TO THE EXISTING STRUCTURE AT THE BATH ROOM ADDITION.
 FBC 106.1.2* CITY AMENDMENTS
  
 7) SPECIFY TERMITE TREATMENT ON THE PLANS AS REQUIRED
 BY SECTION R320.
  
 8) THE MINIMUM INSULATION FOR A RAISED FLOOR SYSTEM IS
 R-11 PER FBC 13-600. SPECIFY THE FLOOR INSULATION ON
 THE PLANS.
  
 9) THE WALL SECTION ON D-1 SPECIFIES THE ROOF SHEATHING
 FASTENERS AS 8D COMMONS. SECTION R803.2.3.1 OF 2006
 REVISIONS TO 2004 FBC RESIDENTIAL CODE REQUIRES 8D RING
 SHANK NAILS.
  
 10)DESIGN DATA NOTE H ON SHEET D-1 FOR THE ONE STORY
 AND A-1 FOR THE SITE WALL INCORRECTLY SPECIFIES THE
 SBCCI. PLEASE REVISE TO REFERENCE THE FBC.
  
 11) SHEET 5 OF 5 APPEARS TO BE MISSING. PLEASE SUBMIT
 MISSING SHEET.
  
 12) PLEASE CLARIFY WHAT IS MEANT BY EXP. B AND EXP. C
 AS SPECIFIED ON THE FLOOR PLAN ON SHEET A-1.
  
 13) SPECIFY THE WINDOW SIZE AND TYPE FOR THE EXISTING
 BATHROOM ON THE FLOOR PLAN ON A-1. FBC 106.1* CITY
 AMENDMENTS
  
 14) SUBMIT (2) TWO COPIES OF THE PRODUCT APPROVALS FOR
 THE ROOF COVERING, SINGLE HUNG WINDOWS AND OUTSWING
 DOORS. SEE DCA RULE 9B-72.
  
 15) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH ONE
 OF THE COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]