| 2008-04-14 14:12:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) FROM THE PLANS SUBMITTED IT APPEARS YOU WISH TO |
| | PRODUCE A TENANT SEPARATION WALL, SEE 2004 FBC 708.1. |
| | |
| | ***SECTION 708FIRE PARTITIONS |
| | |
| | 708.1 GENERAL. |
| | THE FOLLOWING WALL ASSEMBLIES SHALL COMPLY WITH THIS |
| | SECTION. |
| | 1. WALLS SEPARATING DWELLING UNITS IN THE SAME |
| | BUILDING. |
| | 2. WALLS SEPARATING SLEEPING UNITS IN OCCUPANCIES |
| | IN GROUP R-1, HOTEL OCCUPANCIES, R-2 AND I-1. |
| | 3. WALLS SEPARATING TENANT SPACES IN COVERED MALL |
| | BUILDINGS AS REQUIRED BY SECTION 402.7.2 . |
| | 4. CORRIDOR WALLS AS REQUIRED BY SECTION 1016.1 . |
| | 5.WALL SEPARATING INDIVIDUAL TENANT SPACES. |
| | (TENANT SEPARATION WALL). |
| | |
| | EXCEPTIONS: |
| | 1. IN GROUP B AND S OCCUPANCIES WALLS USED TO |
| | SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE |
| | FIRE-RESISTANCE RATING, PROVIDED NO AREA BETWEEN FIRE |
| | PARTITIONS HAVING A 1-HOUR FIRE-RESISTANCE RATING |
| | EXCEEDS 3,000 SQUARE FEET (279 M 2 ). |
| | |
| | 2) PLEASE PROVIDE INFORMATION SHOWING COMPLIANCE WITH |
| | EXCEPTION 1. IF YOU CAN NOT MEET THE EXCEPTION PLEASE |
| | RATE THE WALL AND SHOW HOW ALL PENETRATIONS WILL COMPLY |
| | WITH THE 2004 FBC. |
| | |