| 2008-04-11 09:42:45 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} INDICATE COMPLIANCE WITH THE FOLLOWING: NFPA-72, |
| | 11.5.1.2 NOTIFICATION. |
| | (A)FIRE-WARNING EQUIPMENT FOR DWELLING UNITS SHALL |
| | PROVIDE A SOUND THAT IS AUDIBLE IN ALL OCCUPIABLE |
| | DWELLING AREAS. |
| | (B)WHERE MORE THAN ONE SMOKE OR HEAT ALARM IS |
| | INSTALLED FOR NEW CONSTRUCTION, THEY SHALL BE ARRANGED |
| | SO THAT THE OPERATION OF ANY SMOKE OR HEAT ALARM CAUSES |
| | THE ALARM IN ALL SMOKE AND HEAT ALARMS WITHIN THE |
| | DWELLING UNIT TO SOUND. |
| | |
| | THE SMOKE ALARMS IN THE UNIT MUST BE INTERCONNECTED AND |
| | THEREFORE MUST BE FED FROM ONLY ONE CIRCUIT. IF THAT IS |
| | THE INTENT WITH USING CIRCUIT #17, IN PLACE OF CIRCUITS |
| | #19 AS IN THE PANEL SCHEDULE, THEN DESIGNATE WHICH |
| | PANEL FEEDS THAT CIRCUIT. |
| | |
| | 2} DESIGNATE THE PANELS IN A MANNER THAT ALLOWS CIRCUIT |
| | NUMBERS TO BE IDENTIFIED WITH THE PANEL OF ORIGIN. |
| | |
| | 3} THE DINING ROOM RECEPTACLES ARE ON CIRCUIT #18 IN |
| | THE PANEL SCHEDULE, BUT ONE IS NUMBERED 14 ON THE PLAN. |
| | CORRELATE ALL CIRCUIT NUMBERS WITH PANEL PER COMMENT |
| | #2.EG NO FAMILY ROOM IN THE SCHEDULE. SEE 408.4 CIRCUIT |
| | DIRECTORY OR CIRCUIT IDENTIFICATION |
| | |