| 2008-04-19 08:52:00 | BUILDING PLAN REVIEW |
| | PERMIT: 08040184 |
| | ADD: 1617 N.FLAGLER DR. |
| | CONT: KENNETH M. SALVUCCI INC. |
| | TEL: (561)684-7459 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4-19-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. / |
| | |
| | 3)UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE' |
| | SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A |
| | COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT |
| | FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | |
| | 4)1207.3 SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | PROVIDE THE MANUFACTURE?S SPECIFICATIONS FOR THE CORK |
| | SHOWING COMPLIANCE WITH THIS SECTION. |
| | |
| | 5)SHOW THE NEW LAYOUT OF THE SPRINKLER HEADS IN |
| | RELATION TO THE NEW CONSTRUCTION. FBC 106.3.5.1.1(5) |
| | |
| | 6)FBC 907.2.10.1.2 GROUPS R-2, SINGLE- OR |
| | MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AND |
| | MAINTAINED IN GROUPS R-2, REGARDLESS OF OCCUPANT LOAD |
| | AT ALL OF THE FOLLOWING LOCATIONS: |
| | 1.ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE |
| | SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS. |
| | 2.IN EACH ROOM USED FOR SLEEPING PURPOSES. THERE IS |
| | NO SMOKE ALARM IN THE MASTER BED ROOM OR IN THE |
| | IMMEDIATE VICINITY ON THAT ROOM. |
| | |
| | 7)907.2.10.3 WHERE MORE THAN ONE SMOKE ALARM IS |
| | REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING |
| | UNIT IN GROUP R-2, R-3 OR R-4, OR WITHIN AN INDIVIDUAL |
| | DWELLING UNIT OR SLEEPING UNIT IN GROUP R-1, THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| | THE ACTIVATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| | ALARMS IN THE INDIVIDUAL UNIT. THE ALARM SHALL BE |
| | CLEARLY AUDIBLE IN ALL BEDROOMS OVER BACKGROUND NOISE |
| | LEVELS WITH ALL INTERVENING DOORS CLOSED. |
| | |
| | 8)FOR PLAN REVIEW PURPOSES INDICATE THE TYPE OF |
| | BUILDING PER TABLE 601 AND 602 OF THE FBC 2004 ALSO THE |
| | USE AND OCCUPANCY PER CH. 3 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |