| Plan Review Notes For Permit 08040183 |
| Permit Number |
08040183 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-05-08 13:35:14 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.REVISE THE FLOOR PLAN TO SHOW THE LOCATION OF | | | WORK. | | | | | | 2. SHOW REQUIRED FIRE RESISTANCE RATING FOR THE WALL | | | AND HOW PROPOSED WORK WILL COMPLY.THIS APPEARS TO BE | | | A 1 HOUR EXIT CORRIDOR REQUIRED BY FBC TABLE 1016.1. | | | | | | 3.SEE FBC803.3, STABILITY.THE DATA SUBMITTED FOR | | | THE LIQUID NAIL STATED THAT HIGH HEAT CONDITIONS ARE TO | | | BE AVOIDED.IT DOES NOT APPEAR TO COMPLY WITH THE HEAT | | | REQUIREMENTS OF FBC803.3. | | | | | | 4.HOW HAS THE DETERIORATION OF THE EXISTING DRYWALL | | | AFFECTED REQUIRED FIRE RESISTANCE? | | | | | | 5.GYPSUM BOARD TO BE INSTALLED INACCORDANCE WITH | | | FBC 2508.1.SEE GA 216, A TEST ON THE EXISTING DRYWALL | | | IS REQUIRED, SECTION 12. | | | | | | 6.PROVIDE A DETAIL FOR PROPOSED WORK.INCLUDE SIZE | | | OF DRYWALL, HEIGHT, TYPE. | | | | | | 7.SEE GA 216, WALLPAPER TO BE REMOVED PRIOR TO | | | ADHESION OF NEW DRYWALL.PLEASE NOTE ON THE DETAIL. | | | | | | 8.WHO WILL CERTIFY THE TEST ON THE EXISTING DRYWALL | | | AND FIRE RESISTANCE? | | | |
|