| 2008-05-12 08:23:57 | THIS REVIEW WAS PERFORMED ON PLANS FOR TITLED "CITY |
| | COMMONS AND WATERFORNT DOCKS, NORTH CLEMATIS DOCK |
| | UTILITIES. |
| | |
| | 1. IT DOES NOT APPEAR THAT THE PREVIOUS FIRE RESCUE |
| | PLANS REVIEW NOTES WERE ADDRESSED BY THESE DRAWINGS. |
| | PLEASE DISPLAY NEAREST FIRE HYDRANT. |
| | |
| | 2. THE PORTABLE FIRE EXTINGUISHERS INDICATED ON THE |
| | PLANS NEED TO BE PROPERLY SERVICED TAGGED. |
| | |
| | 3. THE REQUIRED SMOKING RESTRICTIONS AS INDICATED IN |
| | NFPA 303 IS NOT ADDRESSED BY THESE PLANS. |
| | |
| | 4. THE REQUIRED STANDPIPE SYSTEM SHALL MEET THE |
| | REQUIREMENTS OF NFPA 303, THE STANDARD FOR MARINAS AND |
| | BOATYARDS. THE WET CLASS I STANDPIPE SYSTEM SHALL MEET |
| | THE REQUIREMENTS OF NFPA 14, THE STANDARD FOR THE |
| | INSTALLATION OF STANDPIPE, PRIVATE HYDRANT, AND HOSE |
| | SYSTEMS. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | INSTALLATION OF THE STANDPIPE SYSTEM. THE STANDPIPE |
| | SYSTEM WHEN INSTALLED SHALL BE PRESSURE TESTED ALONG |
| | WITH THE PROPOSED FIRE DEPARTMENT CONNECTION (FDC) TO |
| | ENSURE TIGHTNESS. THE HOSE VALVES SHALL BE EQUIPPED |
| | WITH 2 1/2 TO 1 1/2 REDUCERS. THE HOSE VALVES AND |
| | PIOING SHALL BE PROPERLY RESTRAINED. |
| | |
| | 5. ALL ELECTRICAL SYSTEMS AND DEVICES SHALL COMPLY WITH |
| | NFPA 70, THE NATIONAL ELECRICAL CODE AND NFPA 303, THE |
| | STANDARD FOR MARINAS AND BOATYARDS. |
| | |
| | 6. PLEASE INDICATE THE PORPOSED MEANS OF TRANSMITTING |
| | OF AN EMERGENCY AT THIS LOCATION. NFPA 303, REQUIRES |
| | THAT A MEANS TO REPORT AN EMERGENCY SHALL BE PROVIDED |
| | AND IF THIS MEANS IS A TELEPHONE IT SHALL NOT REQUIRE A |
| | COIN TO OPERATE. |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |