| Plan Review Notes For Permit 08040176 |
| Permit Number |
08040176 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-25 14:57:14 | ***DENIED*** | | | | | | 1) IN ADDITION TO OTHER APPLICABLE CODES AND | | | GOVERNMENTAL APPROVAL, WORK SHALL COMPLY WITH NFPA 303, | | | STANDARD FOR MARINAS AND BOATYARDS AND ALL ASSOCIATED | | | PIERS, DOCKS AND FLOATS. | | | | | | 2) PLEASE INDICATE THE MAXIMUM HOSE LAY DISTANCE FROM | | | THE FIRE APPARATUS. FIRE STANDPIPE SYSTEM SHALL BE | | | REQUIRED IF THE DISTANCE EXCEEDS 150 FEET. IF THE SCOPE | | | OF THIS WORK DOES NOT APPLY, PLEASE NOTE THIS | | | REQUIREMENT FOR FUTURE REFERENCE WITH REGARD TO THE | | | PROPOSED PIER AND GANGWAY, AND FLOATING DOCKS. | | | | | | 3) PLEASE ILLUSTRATE THE CLOSEST FIRE HYDRANTS TO THIS | | | PROJECT. | | | | | | 4) PLEASE SEE BUILDING REVIEW COMMENT REGARDING GUARDS | | | AND HANDRAILS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|