| Date |
Text |
| 2008-06-03 13:29:48 | PLUMBING PLAN REVIEW: |
| | DENIED 3RD TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. RESUBMITTED SHEETS P.1 AND P.2, DO NOT HAVE THE |
| | REQUIRED ARCHITECTS SEAL. PLEASE HAVE THE DESIGN |
| | PROFESSIONAL SEAL SHEETS P.1 AND P.2. PER FLORIDA |
| | STATUTES 481.221(2). |
| | |
| | 2. REMOVE NONCOMPLIANT P.1 AND P.2 SHEETS FROM |
| | SUBMITTED PERMIT SETS OF PLANS AND PLACE ONLY COMPLIANT |
| | SHEETS P.1 AND P.2 IN RESUBMITEED SETS. PER (W.P.B. AS |
| | AMENDED) SECTION 106.1.3 QUALITY OF BUILDING PLANS. THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, STANDARDS FOR PLANS AND SPECIFICATIONS, IN |
| | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM |
| | SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED |
| | TO RECORDS MANAGEMENT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |