| 2008-05-09 13:29:25 | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S |
| | RESPONSE FOR PURPOSE OF CONTINUITY. |
| | |
| | 1. PLEASE INDICATE THE CORRECT ADDRESS IN THE TITLE |
| | BLOCK ON ALL SHEETS. PER (W.P.B.) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | **RESPONSE NOTED, HOWEVER PLEASE REFERENCE ATTACHED |
| | PROPERTY APPRAISER INFORMATION WITH THE PERMIT |
| | APPLICATION PARCEL NUMBER THAT STATES THE ADDRESS AS |
| | 5101 CONGRESS AVE. PLEASE INDICATE THE CORRECT ADDRESS |
| | ON ALL SHEETS. |
| | |
| | 2. "OK" COMMENT ADDRESSED. |
| | |
| | 3. SHEET P.1 WATER HEATER PIPING DIAGRAM AND EWH PAN |
| | DRAIN IN BATHROOM #113: THE WATER HEATER PAN DRAIN STUB |
| | 1" BELOW CEILING SURFACE OVER THE LAVATORY IN BATHROOM |
| | #113 IS UNACCEPTABLE FOR A TERMINATION OVER A SUITABLE |
| | LOCATION. THE ONLY FIXTURE THAT IS ACCEPTABLE FOR THIS |
| | IS A MOP SINK. |
| | 504.7.2 PAN DRAIN TERMINATION. |
| | THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER |
| | A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR |
| | DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING AND |
| | TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE |
| | THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND |
| | SURFACE. |
| | **RESPONSE NOTED HOWEVER THE RESUBMITTED SHEETS P.1 |
| | AND P.2 ARE NOW INDICATING THE PAN DRAIN AS BEING ABOVE |
| | THE CEILING DRAINING INTO AN 1-1/2 INCH TRAP. THIS IS |
| | NOT A SUITABLY LOCATED INDIRECT WASTE RECEPTOR. A |
| | SUITABLY LOCATED WASTE RECEPTOR IS ONE LOCATED OUT IN |
| | THE OPEN SO THE HEATER PAN WILL BE OBSERVED DRAINING |
| | AND THAT THERE IS A PROPBLEM WITH THE WATER HEATER, NOT |
| | IN A CLOSED DROP CEILING AREA. ALSO A WASTE RECEPTOR OR |
| | FLOOR DRAIN WITH A TRAP WILL NEED A TRAP SEAL PRIMER |
| | VALVE, PER FBC-2004 PLUMBING SECTION 1002.4 TRAP SEALS. |
| | WHERE A TRAP SEAL IS SUBJECT TO LOSS BY EVAPORATION, A |
| | TRAP SEAL PRIMER VALVE SHALL BE INSTALLED. A TRAP SEAL |
| | PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR ASSE 1044. |
| | |
| | 4. "OK" COMMENT ADDRESSED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |