Plan Review Notes
Plan Review Notes For Permit 08040166
Permit Number 08040166
Review Stop P
Sequence Number 2
Notes
Date Text
2008-05-09 13:29:25PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S
 RESPONSE FOR PURPOSE OF CONTINUITY.
  
 1. PLEASE INDICATE THE CORRECT ADDRESS IN THE TITLE
 BLOCK ON ALL SHEETS. PER (W.P.B.) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 **RESPONSE NOTED, HOWEVER PLEASE REFERENCE ATTACHED
 PROPERTY APPRAISER INFORMATION WITH THE PERMIT
 APPLICATION PARCEL NUMBER THAT STATES THE ADDRESS AS
 5101 CONGRESS AVE. PLEASE INDICATE THE CORRECT ADDRESS
 ON ALL SHEETS.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. SHEET P.1 WATER HEATER PIPING DIAGRAM AND EWH PAN
 DRAIN IN BATHROOM #113: THE WATER HEATER PAN DRAIN STUB
 1" BELOW CEILING SURFACE OVER THE LAVATORY IN BATHROOM
 #113 IS UNACCEPTABLE FOR A TERMINATION OVER A SUITABLE
 LOCATION. THE ONLY FIXTURE THAT IS ACCEPTABLE FOR THIS
 IS A MOP SINK.
 504.7.2 PAN DRAIN TERMINATION.
 THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER
 A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR
 DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING AND
 TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE
 THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND
 SURFACE.
 **RESPONSE NOTED HOWEVER THE RESUBMITTED SHEETS P.1
 AND P.2 ARE NOW INDICATING THE PAN DRAIN AS BEING ABOVE
 THE CEILING DRAINING INTO AN 1-1/2 INCH TRAP. THIS IS
 NOT A SUITABLY LOCATED INDIRECT WASTE RECEPTOR. A
 SUITABLY LOCATED WASTE RECEPTOR IS ONE LOCATED OUT IN
 THE OPEN SO THE HEATER PAN WILL BE OBSERVED DRAINING
 AND THAT THERE IS A PROPBLEM WITH THE WATER HEATER, NOT
 IN A CLOSED DROP CEILING AREA. ALSO A WASTE RECEPTOR OR
 FLOOR DRAIN WITH A TRAP WILL NEED A TRAP SEAL PRIMER
 VALVE, PER FBC-2004 PLUMBING SECTION 1002.4 TRAP SEALS.
 WHERE A TRAP SEAL IS SUBJECT TO LOSS BY EVAPORATION, A
 TRAP SEAL PRIMER VALVE SHALL BE INSTALLED. A TRAP SEAL
 PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR ASSE 1044.
  
 4. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]