| Date |
Text |
| 2008-04-15 11:59:56 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PLEASE INDICATE THE CORRECT ADDRESS IN THE TITLE |
| | BLOCK ON ALL SHEETS. PER (W.P.B.) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. SHEET A.0 CLEARLY INDICATE THE FOLLOWING |
| | REQUIREMENTS FOR THE SINK DEMO ON THE RESUBMITTAL.PER |
| | FBC-2004 PLUMBING, SECTION 704.5 |
| | DEAD ENDS: IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | A PLUMBING PERMIT REQUIRED AND |
| | INSPECTION REQUIRED OF DEMO WORK PRIOR |
| | TO COVERING DEMO WORK WITH FINNISH |
| | WALLS, CIELINGS, OR POURED CONCRETE |
| | SLABS. |
| | |
| | 3. SHEET P.1 WATER HEATER PIPING DIAGRAM AND EWH PAN |
| | DRAIN IN BATHROOM #113: THE WATER HEATER PAN DRAIN STUB |
| | 1" BELOW CEILING SURFACE OVER THE LAVATORY IN BATHROOM |
| | #113 IS UNACCEPTABLE FOR A TERMINATION OVER A SUITABLE |
| | LOCATION. THE ONLY FIXTURE THAT IS ACCEPTABLE FOR THIS |
| | IS A MOP SINK. |
| | 504.7.2 PAN DRAIN TERMINATION. |
| | THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER |
| | A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR |
| | DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING AND |
| | TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE |
| | THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND |
| | SURFACE. |
| | |
| | 4. SHEET P.1 WATER HEATER PIPING DIAGRAM: THERMAL |
| | EXPANSION CONTROL FOR THE WATER HEATER IS REQUIRED. |
| | 607.3.2 BACKFLOW PREVENTION DEVICE OR CHECK VALVE. |
| | WHERE A BACKFLOW PREVENTION DEVICE, CHECK VALVE OR |
| | OTHER DEVICE IS INSTALLED ON A WATER SUPPLY SYSTEM |
| | UTILIZING STORAGE WATER HEATING EQUIPMENT SUCH THAT |
| | THERMAL EXPANSION CAUSES AN INCREASE IN PRESSURE, A |
| | DEVICE FOR CONTROLLING PRESSURE SHALL BE INSTALLED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |