| 2008-04-11 15:29:49 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THERE ARE TWO DIFFERENT GENERATOR OPERATING DATA |
| | SHEETS SUBMITTED FOR THE 35 KW GENERATOR INDICATING TWO |
| | DIFFERENT BTU LOADS. PLEASE CORRELATE THE RESUBMITTAL |
| | WITH ONLY ONE DATA SHEET. PER FBC FUEL GAS SECTION |
| | 401.1 SCOPE. |
| | |
| | 2. CLEARLY INDICATE THE CORRESPONDING LENGTHS TO ALL |
| | CUT SECTIONS OF PIPE. THE ONLY CUT SECTION OF PIPE WITH |
| | A CORRESPONDING LENGTH IS THE UNDERGROUND PE PIPE . |
| | WHAT ARE THE CORRESPONDING LENGTHS TO THE ABOVE GROUND |
| | PIPING. PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | **NEED PRINTED NAME, DATE AND SIGNATURES ON THE |
| | RESUBMITTED GAS ISOMETRIC RISER DIAGRAM. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |