| Plan Review Notes For Permit 08040136 |
| Permit Number |
08040136 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-15 15:39:28 | | | | | | | DENIED | | | | | | 1)THE 2006 AMENDMENTS TO THE 2004 FBC REQUIRE | | | BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN THAT IS | | | DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS OPEN | | | GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF 600 | | | FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C | | | CATEGORY. PLEASE ADJUST THE DESIGN PARAMETERS AND WIND | | | PRESSURES ACCORDINGLY | | | | | | 2)SHUTTER PERMIT APPLICATIONS REQUIRE 2 COPIES OF A | | | KEY PLAN (WITH EGRESS AND OPENING SIZES SHOWN), SHUTTER | | | SCHEDULE AND THE PRODUCT APPROVALS. APPROVAL DRAWINGS | | | SHALL BE MARKED FOR MOUNTING METHOD AND CONNECTION TYPE | | | AND THE SCHEDULE FILLED OUT WITH ALL PERTINENT | | | INFORMATION SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION, | | | MOUNTING CONNECTION METHOD, ANCHOR TYPE & ON CENTER | | | SPACING, SHUTTER SPAN (VERTICAL OR HORIZONTAL), ETC.) | | | PLEASE SEE THE ATTACHED MEMO AND SCHEDULE. | | | | | | 3)EGRESS FROM THE BUILDING CANNOT BE THROUGH THE | | | GARAGE DOOR, KEY PLAN SHOWS PANELS ON THE EGRESS DOOR. | | | ONLY GLAZED OPENING IN WIND BORNE DEBRIS REGIONS | | | REQUIRE IMPACT RESISTANT COVERINGS IF DOOR HAS NO | | | GLAZING PANEL WOULD NOT BE NECESSARY | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|