| 2008-10-06 14:30:41 | NO CIVIL PLAN SUBMITTED. CIVIL PLAN WAS SUBMITTED TO | | | ENGINEERING SERVICES DEPARTMENT AT 1000-45TH STREET ON | | | 9-16-08. IT WAS GIVEN TO MANNY GONZALEZ FOR REVIEW ON | | | 9-25-08. PLAN NEEDS TO SHOW: | | | 1-SILT FENCE NEEDS TO BE INSTALLED AROUND ANY AREAS TO | | | BE DISTURBED (NEW BUILDING SITE, TRENCH FROM NEW | | | BUILDING TO EXISTING FOR ELECTRICAL CONDUITS). | | | 2-FILTER FABRIC IS REQUIRED UNDER THE TWO CATCH BASINS | | | GRATES ON SITE TO STOP SOLIDS FROM ENTER THE SYSTEM. | | | THEY ALSO NEED TO BE CLEANED AS NEEDED. | | | 3-NEED IMPERVIOUS/PERVIOUS INFORMATION FOR BEFORE AND | | | AFTER DEVELOPMENT. |
|