| 2008-10-07 08:48:14 | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE CONTACT THIS OFFICE/REVIEWER TO GO OVER ANY |
| | OF THE COMMENTS |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| | CALCULATIONS SHOWN ON SHEET 3 ARE SHOWN AS A MINIMUM |
| | DESIGN. THE SECTION OF THE ENERGY CODE GIVEN ON |
| | PREVIOUS REVIEW AND THE INTENT OF CHAPTER 13 IS TO |
| | LIMIT THE AMOUNT OF WATTS PER SQ FT. THIS SHOULD HAVE |
| | BEEN DONE AS A MAXIMUM OF THE WATTS PER SQ FT. BASED ON |
| | THE .8 WHICH WAS APPARENTLY TAKEN FROM TABLE 13-415.2.B |
| | AND THE FIXTURES ON PLANS, THE DESIGN WOULD BE OVER THE |
| | ALLOWANCE. THERE WERE NO ALLOWANCES SHOWN FOR EXTERIOR. |
| | PLEASE PROVIDE ALL FIXTURES. |
| | THE SECTIONS NOTED ON PREVIOUS REVIEW 13-415.2 |
| | ABC.1.1,.1.2 AND .1.3. |
| | PLEASE CALL TO GO OVER SO THE DESIGN AND ALLOWANCE WILL |
| | BE CODE COMPLIANT FOR USE/OCCUPANCY. |
| | |
| | 2) NOTE: PLEASE SEE THE EXHAUST FAN AT THE GABLE END |
| | NEEDS TO BE ON A DEDICATED CIRCUIT. THE 3/4 HP MOTOR |
| | BASED ON TABLE 430.248 PLACES THE AMPERAGE AT 13.8AMPS. |
| | AS THE VA RATING IS ABOVE 750VA, AND A MOTOR CIRCUIT |
| | THIS WOULD REQUIRE A DEDICATED CIRCUIT. THIS IS |
| | CURRENTLY BEING SHOWN ON CIRCUIT B-8 WHICH IS A 120V |
| | CIRCUIT FEEDING OTHER WALL RECEPTACLES IN SPACE. |
| | |
| | 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM MAIN AT THE DETACHED BUILDING TO THE NEW |
| | SUB PANEL *P2* AS DESIGNATED ON RISER. THE PLANS CALL |
| | THIS PANEL AS *B*. THE DESIGNATIONS APPEAR TO BE A |
| | MISPRINT. |
| | PLEASE SIZE THE EQUIPMENT GROUND PER 250.122. |
| | 250.6,250.24,250.110,250.32 ETC |
| | |
| | 4) NOTE: PLEASE SEE NEC 220 FOR LOAD CALCULATIONS. |
| | PLEASE CLARIFY IF THE LOAD CALCULATIONS AS SHOWN ARE |
| | FOR THE ENTIRE SERVICE OR FOR THE NEW BUILDING ONLY? IF |
| | FOR ENTIRE SERVICE SEE NOTES BELOW AND ALSO PROVIDE |
| | LOAD ON PANEL FOR NEW BUILDING AS THERE IS NO TOTAL |
| | LOAD AT THE BOTTOM OF PANEL *B/P2*. |
| | IF THIS CALCULATION IS FOR THE ENTIRE SERVICE THEN |
| | PLEASE SEE NEC 220 FOR ALL OTHER LOADS INCLUDING KNOWN |
| | LIGHT LOADS. IF THIS LOAD CALCULATION IS ONLY FOR THIS |
| | NEW BUILDING PLEASE VERIFY WHY THE A/C IS ON THIS |
| | PANEL. |
| | PLEASE SEE SOME SPECIFIC SECTIONS WOULD BE 220.18, |
| | 220.50, 220.14(D)(E) AND (F). |
| | |
| | WHEN SIZING A SERVICE WITH UNKNOWN LOADS THE CODE |
| | PROVIDES TABLES FOR MINIMUM VA PER SQ FT AND MINIMUM VA |
| | PER RECEPTACLE ETC HOWEVER WHEN KNOWN LIGHTING LOADS |
| | AND DEDICATED LOADS ARE SHOWN AND BEING INSTALLED THEN |
| | THE SIZING OF THE CIRCUITS AND THE SERVICE ARE REQUIRED |
| | TO MEET THE SPECIFIC SECTIONS. THE DE-RATINGS ARE |
| | PERMITTED ONCE DEDICATED KNOWN LOADS ARE FIGURED. |
| | AS THERE IS NO FIXTURE LEGEND SHOWN AND ONLY THE |
| | INTERIOR FIXTURES IN NEW BUILDING ARE NOTED AS 250VA |
| | THE FINAL LOADS CAN NOT BE VERIFIED TO SEE WHICH IS THE |
| | LARGER OF LOADS. |
| | |
| | |
| | ** AS NOTED ABOVE, PLEASE CONTACT THIS OFFICE TO GO |
| | OVER COMMENTS FOR ANY CLARIFICATION OR QUESTIONS. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |