Plan Review Notes
Plan Review Notes For Permit 08040135
Permit Number 08040135
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-07 08:48:14 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE CONTACT THIS OFFICE/REVIEWER TO GO OVER ANY
 OF THE COMMENTS
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS SHOWN ON SHEET 3 ARE SHOWN AS A MINIMUM
 DESIGN. THE SECTION OF THE ENERGY CODE GIVEN ON
 PREVIOUS REVIEW AND THE INTENT OF CHAPTER 13 IS TO
 LIMIT THE AMOUNT OF WATTS PER SQ FT. THIS SHOULD HAVE
 BEEN DONE AS A MAXIMUM OF THE WATTS PER SQ FT. BASED ON
 THE .8 WHICH WAS APPARENTLY TAKEN FROM TABLE 13-415.2.B
 AND THE FIXTURES ON PLANS, THE DESIGN WOULD BE OVER THE
 ALLOWANCE. THERE WERE NO ALLOWANCES SHOWN FOR EXTERIOR.
 PLEASE PROVIDE ALL FIXTURES.
 THE SECTIONS NOTED ON PREVIOUS REVIEW 13-415.2
 ABC.1.1,.1.2 AND .1.3.
 PLEASE CALL TO GO OVER SO THE DESIGN AND ALLOWANCE WILL
 BE CODE COMPLIANT FOR USE/OCCUPANCY.
  
 2) NOTE: PLEASE SEE THE EXHAUST FAN AT THE GABLE END
 NEEDS TO BE ON A DEDICATED CIRCUIT. THE 3/4 HP MOTOR
 BASED ON TABLE 430.248 PLACES THE AMPERAGE AT 13.8AMPS.
 AS THE VA RATING IS ABOVE 750VA, AND A MOTOR CIRCUIT
 THIS WOULD REQUIRE A DEDICATED CIRCUIT. THIS IS
 CURRENTLY BEING SHOWN ON CIRCUIT B-8 WHICH IS A 120V
 CIRCUIT FEEDING OTHER WALL RECEPTACLES IN SPACE.
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN AT THE DETACHED BUILDING TO THE NEW
 SUB PANEL *P2* AS DESIGNATED ON RISER. THE PLANS CALL
 THIS PANEL AS *B*. THE DESIGNATIONS APPEAR TO BE A
 MISPRINT.
 PLEASE SIZE THE EQUIPMENT GROUND PER 250.122.
 250.6,250.24,250.110,250.32 ETC
  
 4) NOTE: PLEASE SEE NEC 220 FOR LOAD CALCULATIONS.
 PLEASE CLARIFY IF THE LOAD CALCULATIONS AS SHOWN ARE
 FOR THE ENTIRE SERVICE OR FOR THE NEW BUILDING ONLY? IF
 FOR ENTIRE SERVICE SEE NOTES BELOW AND ALSO PROVIDE
 LOAD ON PANEL FOR NEW BUILDING AS THERE IS NO TOTAL
 LOAD AT THE BOTTOM OF PANEL *B/P2*.
 IF THIS CALCULATION IS FOR THE ENTIRE SERVICE THEN
 PLEASE SEE NEC 220 FOR ALL OTHER LOADS INCLUDING KNOWN
 LIGHT LOADS. IF THIS LOAD CALCULATION IS ONLY FOR THIS
 NEW BUILDING PLEASE VERIFY WHY THE A/C IS ON THIS
 PANEL.
 PLEASE SEE SOME SPECIFIC SECTIONS WOULD BE 220.18,
 220.50, 220.14(D)(E) AND (F).
  
 WHEN SIZING A SERVICE WITH UNKNOWN LOADS THE CODE
 PROVIDES TABLES FOR MINIMUM VA PER SQ FT AND MINIMUM VA
 PER RECEPTACLE ETC HOWEVER WHEN KNOWN LIGHTING LOADS
 AND DEDICATED LOADS ARE SHOWN AND BEING INSTALLED THEN
 THE SIZING OF THE CIRCUITS AND THE SERVICE ARE REQUIRED
 TO MEET THE SPECIFIC SECTIONS. THE DE-RATINGS ARE
 PERMITTED ONCE DEDICATED KNOWN LOADS ARE FIGURED.
 AS THERE IS NO FIXTURE LEGEND SHOWN AND ONLY THE
 INTERIOR FIXTURES IN NEW BUILDING ARE NOTED AS 250VA
 THE FINAL LOADS CAN NOT BE VERIFIED TO SEE WHICH IS THE
 LARGER OF LOADS.
  
  
 ** AS NOTED ABOVE, PLEASE CONTACT THIS OFFICE TO GO
 OVER COMMENTS FOR ANY CLARIFICATION OR QUESTIONS.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  