2008-05-06 15:38:35*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE WITH
 EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OOR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES) .
  
 3. SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  