| Plan Review Notes For Permit 08040125 |
| Permit Number |
08040125 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-08 09:31:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE. | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3, | | | PROVIDE CALCULATIONS. | | | | | | 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9B72, WWW.FLORIDABUILDING.ORG.THIS IS REQUIRED IN | | | ADDITION TO THE NOAS PROVIDED. | | | | | | 3.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 505.1.THE EXISTING CLEAR | | | OPENING CANNOT BE REDUCED BY MORE THAN 5%; NO | | | INFORMATION WAS PROVIDED REGARDING THE EXISTING | | | WINDOWS. | | | | | | 4.IF ENGINEERING IS INCLUDED IN THE PACKAGE, IT MUST | | | COMPLY WITH FAC61G15-23.002.A LEGIBLE SEAL IS | | | REQUIRED AND TWO ORIGINAL SETS ARE TO BE INCLUDED FOR | | | PERMIT ISSUANCE. | | | |
|