2008-04-08 09:31:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2.PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE.
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3,
 PROVIDE CALCULATIONS.
  
 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.THIS IS REQUIRED IN
 ADDITION TO THE NOAS PROVIDED.
  
 3.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.THE EXISTING CLEAR
 OPENING CANNOT BE REDUCED BY MORE THAN 5%; NO
 INFORMATION WAS PROVIDED REGARDING THE EXISTING
 WINDOWS.
  
 4.IF ENGINEERING IS INCLUDED IN THE PACKAGE, IT MUST
 COMPLY WITH FAC61G15-23.002.A LEGIBLE SEAL IS
 REQUIRED AND TWO ORIGINAL SETS ARE TO BE INCLUDED FOR
 PERMIT ISSUANCE.
  