| Date |
Text |
| 2008-09-03 11:59:44 | GAS PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE THE |
| | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS |
| | WITH NO CORRESPONDING LENGTHS. |
| | |
| | 2. NOT ALL PIPIE SIZES AND MATERIAL TYPES ARE BEING |
| | INDICATED ON THE GAS RISER. PLEASE CLEARLY INDICATE THE |
| | PIPE SIZES AND MATERIAL TYPES OF THE ABOVE GROUND |
| | PIPING AT THE METER LOCATION AND TO THE EXISTING STOVE. |
| | PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | *NOTE: CLEARLY INDICATE IF THE GAS METER ALSO DELIVERS |
| | GAS TO THE GARAGE AND GUEST HOUSE ON PERMIT #08040121. |
| | IF THIS GAS METER DOES DELIVER GAS TO THE GARAGE AND |
| | GUEST HOUSE CLEARLY INDICATE THAT IT DOES AND CLEARLY |
| | INDICATE THE BTU'S OF THE GARAGE/GUEST HOUSE |
| | (GARAGE/GUEST HOUSE HAS A 140,000 BTU WATER HEATER; |
| | 22,000 BTU DRYER; AND A 65,000 BTU RANGE). |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: CLEARLY INDICATE THE LONGEST LENGTH OF THE |
| | SYSTEM. THIS INCLUDES THE GARAGE/GUEST HOUSE (SEE |
| | COMMENT #2). PLEASE KNOW THE THE ADDED SUM OF THE |
| | INDICATED CUT SECTION CORRESPONDING LENGTHS IS 110', |
| | HOWEVER THE SUBMITTED GAS ISOMETRIC INDICATES 108'. |
| | PLEASE KNOW THE THE LONGEST LENGTH OF 108' IS WRONG AND |
| | THAT IT NEEDS TO BE CORRELATED WITH COMMENT #1 ON THE |
| | RESUBMITTAL. |
| | |
| | 5. CLEARLY INDICATE IF THE MP REGULATORS (2 PSI TO O.5 |
| | PSI) ARE NEW OR EXISTING ON THE RESUBMITTAL. IF THEY |
| | ARE NEW PLEASE SUBMIT MANUFACTURE SHEETS FOR THE MP |
| | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. |
| | MANUFACTURE SHEETS SHALL CLEARLY INDICATE THE MAKE, |
| | MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A |
| | RECOGNIZED TESTING LABORATORY (LISTING EXAMPLES = CSA, |
| | AGA, UL) |
| | |
| | 6. CLEARLY INDICATE THAT THE FUTURE GAS FIRE PLACE LOGS |
| | ARE CAPPED GAS TIGHT. PER FBC-2004 FUEL GAS SEC. 404.12 |
| | OUTLET CLOSURES: GAS OUTLETS THAT DO NOT CONNECT TO |
| | APPLIANCES SHALL BE CAPPED GAS TIGHT. |
| | |
| | 7. SHEETS A2.1 AND A2.2, DO NOT INDICATE A FUTURE GAS |
| | FIRE PLACE LOGS ON THE MAIN HOUSE FLOOR PLAN. PLEASE |
| | PROVIDE A REVISED PLAN SHEET WITH THE LOCATION OF THE |
| | FUTURE GAS FIRE PLACE LOGS. PER (W.P.B. AS AMENDED) |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |