Plan Review Notes
Plan Review Notes For Permit 08040121
Permit Number 08040121
Review Stop M
Sequence Number 3
Notes
Date Text
2008-08-27 14:19:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN
 *** DENIED ***
  
 1) MECHANICAL PLAN ON FILE WAS SIGNED AND SEALED BY AN
 ARCHITECT (DAVID LAWRENCE) AND ONLY HE MAY MAKE
 REVISIONS.
  
 2) REVISED MECHANICAL PLAN EQUIPMENT SCHEDULE IS
 SHOWING A 13 SEER SYSTEM, ENERGY CALCULATIONS ON FILE
 ARE CALLING FOR A 14 SEER SYSTEM THAT'S A HEAT PUMP.
 PLEASE CORRECT PLAN OR REVISE ENERGY CAL'S, PER 2004
 FBC 13-103.1.2.
  
 3) A/C SYSTEM MODEL NUMBER A.H.U. 19HX5 WITH C.U.
 2TTR3018 (FIRST COMPANY AND TRANE) LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE OR A MANUFACTURER'S DATA SHEET, PER 2004
 FBC 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]