| Plan Review Notes For Permit 08040121 |
| Permit Number |
08040121 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-07-01 13:59:40 | TRUSS SUBMITTAL | | | | | | DENIED BY BUILDING | | | | | | 1) THE PROJECT NAME AND ADDRESS ON THE TRUSS DRAWING | | | COVER SHEET IS NOT CORRECT. FAC 61G15-23.002 | | | | | | 2) THE TRUSS ENGINEER'S WET SIGNATURE IS REQUIRED ON | | | THE DOCUMENTS. THE COVERSHEETS AND TRUSS LAYOUT PLANS | | | ARE NOT ORIGINAL SIGNATURES. PHOTOCOPIES AND SIGNATURE | | | STAMPS ARE NOT ACCEPTABLE. FS471 AND FAC 61G15-23.002 | | | | | | 3) THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED | | | TO REVIEW AND APPROVE THE TRUSS LAYOUT. | | | | | | NOTE: THE TRUSS INFORMATION IS NOT REQUIRED TO BE | | | SUBMITTED FOR PLAN REVIEW. IT IS TO BE GIVEN TO THE | | | BUILDING INSPECTOR IN THE FIELD AT THE ROOF FRAMING | | | INSPECTION. THE ABOVE CORRECTIONS ARE REQUIRED TO BE | | | COMPLETED PRIOR TO THE INSPECTION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|