Plan Review Notes
Plan Review Notes For Permit 08040121
Permit Number 08040121
Review Stop B
Sequence Number 3
Notes
Date Text
2008-07-01 13:59:40TRUSS SUBMITTAL
  
 DENIED BY BUILDING
  
 1) THE PROJECT NAME AND ADDRESS ON THE TRUSS DRAWING
 COVER SHEET IS NOT CORRECT. FAC 61G15-23.002
  
 2) THE TRUSS ENGINEER'S WET SIGNATURE IS REQUIRED ON
 THE DOCUMENTS. THE COVERSHEETS AND TRUSS LAYOUT PLANS
 ARE NOT ORIGINAL SIGNATURES. PHOTOCOPIES AND SIGNATURE
 STAMPS ARE NOT ACCEPTABLE. FS471 AND FAC 61G15-23.002
  
 3) THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED
 TO REVIEW AND APPROVE THE TRUSS LAYOUT.
  
 NOTE: THE TRUSS INFORMATION IS NOT REQUIRED TO BE
 SUBMITTED FOR PLAN REVIEW. IT IS TO BE GIVEN TO THE
 BUILDING INSPECTOR IN THE FIELD AT THE ROOF FRAMING
 INSPECTION. THE ABOVE CORRECTIONS ARE REQUIRED TO BE
 COMPLETED PRIOR TO THE INSPECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]