2008-04-15 09:28:50PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEETS A4.1 AND A5.1 THE SCUPPERS WILL REQUIRE A
 DOWNSPOUT PER FBC BUILDING SECTION
 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 2. SHEET A7.1 SANITARY PLUMBING RISER PLEASE CORRECT
 THE FOLLOWING.
  
 A} CLEARLY INDICATE A TW0-WAY CLEANOUT BEING USED AT
 THE JUNCTION OF THE BUILBING DRAIN AND BUILDING SEWER.
 PER FBC PLUMBING SECTION 708.3.5 BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 B} THE BRANCH DRAIN AND STACK FOR THE WASHING MACHINE
 SHALL BE A MINIMUM OF 3 INCH. PER FBC PLUMBING SECTION
 406.3 WASTE CONNECTION.
  
 C} THE CLEANOUT FOR THE WASHING MACHINE SHALL BE 3
 INCH. PER FBC PLUMBING SECTION 708.7 MINIMUM SIZE.
  
 D} THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT 4 FEET ABOVE FINNISH FLOOR. PER FBC PLUMBING
 SECTION 708.9 ACCESS.
  
 E} IF IT IS THE INTENT TO INSTALL A CLEANOUT FOR THE
 2ND FLOOR LAVATORY IT SHALL BE 2 INCH. PER FBC PLUMBING
 SECTION 708.7 MINIMUM SIZE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER