| 2008-04-15 09:28:50 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEETS A4.1 AND A5.1 THE SCUPPERS WILL REQUIRE A |
| | DOWNSPOUT PER FBC BUILDING SECTION |
| | 1503.6 PROTECTION AGAINST DECAY AND TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 2. SHEET A7.1 SANITARY PLUMBING RISER PLEASE CORRECT |
| | THE FOLLOWING. |
| | |
| | A} CLEARLY INDICATE A TW0-WAY CLEANOUT BEING USED AT |
| | THE JUNCTION OF THE BUILBING DRAIN AND BUILDING SEWER. |
| | PER FBC PLUMBING SECTION 708.3.5 BUILDING DRAIN AND |
| | BUILDING SEWER JUNCTION. |
| | |
| | B} THE BRANCH DRAIN AND STACK FOR THE WASHING MACHINE |
| | SHALL BE A MINIMUM OF 3 INCH. PER FBC PLUMBING SECTION |
| | 406.3 WASTE CONNECTION. |
| | |
| | C} THE CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 |
| | INCH. PER FBC PLUMBING SECTION 708.7 MINIMUM SIZE. |
| | |
| | D} THE CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | LOCATED AT 4 FEET ABOVE FINNISH FLOOR. PER FBC PLUMBING |
| | SECTION 708.9 ACCESS. |
| | |
| | E} IF IT IS THE INTENT TO INSTALL A CLEANOUT FOR THE |
| | 2ND FLOOR LAVATORY IT SHALL BE 2 INCH. PER FBC PLUMBING |
| | SECTION 708.7 MINIMUM SIZE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |