| 2008-04-10 08:24:17 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ONE COPY OF THE ENERGY CALCULATIONS HAVE NOT BEEN |
| | SIGNED BY THE OWNER/AGENT, PLEASE CORRECT PER 2004 FBC |
| | 13-103.3. |
| | |
| | 2) GAS WATER HEATER AND GAS CLOTHES DRYER APPEAR TO BE |
| | IN A CONFINED SPACE. PLEASE ADD COMBUSTION AND MAKE-UP |
| | AIR CALCULATIONS TO MECHANICAL PLAN AND IF NEEDED |
| | PROVIDE COMBUSTION AND MAKE-UP AIR TO SPACE, PER 2004 |
| | FBC/R G2407.1, G207.4, AND G2407.5.1. PLEASE ALSO CHECK |
| | THE BTU'S FOR THE GAS TANKLESS WATER HEATER AS MOST |
| | UNITS OPERATE AT 118,00 BTU'S OR MORE. |
| | |
| | 3) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S FOR THE GAS TANKLESS WATER HEATER, PER |
| | 2004 WPB AMEND. 106.1.2. |
| | |
| | 4)A/C SYSTEM LISTED ON A/C EQUIPMENT SCHEDULE COULD |
| | NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE |
| | CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC |
| | 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1. |
| | |
| | 5) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S FOR THE A/C SYSTEM SHOWING A CARRIER |
| | CONDENSER AND FIRST COMPANY AIR HANDLER HAVE BEEN |
| | DESIGNED AND TESTED TOGETHER TO RATE A 14 SEER, PER |
| | 13-607.1.ABC.3.1. |
| | |