Plan Review Notes
Plan Review Notes For Permit 08040121
Permit Number 08040121
Review Stop M
Sequence Number 1
Notes
Date Text
2008-04-10 08:24:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ONE COPY OF THE ENERGY CALCULATIONS HAVE NOT BEEN
 SIGNED BY THE OWNER/AGENT, PLEASE CORRECT PER 2004 FBC
 13-103.3.
  
 2) GAS WATER HEATER AND GAS CLOTHES DRYER APPEAR TO BE
 IN A CONFINED SPACE. PLEASE ADD COMBUSTION AND MAKE-UP
 AIR CALCULATIONS TO MECHANICAL PLAN AND IF NEEDED
 PROVIDE COMBUSTION AND MAKE-UP AIR TO SPACE, PER 2004
 FBC/R G2407.1, G207.4, AND G2407.5.1. PLEASE ALSO CHECK
 THE BTU'S FOR THE GAS TANKLESS WATER HEATER AS MOST
 UNITS OPERATE AT 118,00 BTU'S OR MORE.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S FOR THE GAS TANKLESS WATER HEATER, PER
 2004 WPB AMEND. 106.1.2.
  
 4)A/C SYSTEM LISTED ON A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 5) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S FOR THE A/C SYSTEM SHOWING A CARRIER
 CONDENSER AND FIRST COMPANY AIR HANDLER HAVE BEEN
 DESIGNED AND TESTED TOGETHER TO RATE A 14 SEER, PER
 13-607.1.ABC.3.1.
  
 MECHANICAL PLAN REVIEW BY;