2008-04-15 10:01:00GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW ON SHEET A7.1 GAS PIPING ISOMETRIC TO
 MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 *NOTE: NOT ALL CUT SECTIONS OF PIPE ARE INDICATING
 CORRESPONDING LENGTHS. PLEASE REFERENCE THE RED CIRCLED
 YELLOW HIGH LIGHTED CUT SECTIONS THAT REQUIRE
 CORRESPONDING LENGTHS. PER FBC FUEL GAS SECTION 401.1
 SCOPE.
  
 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 *NOTE: BTU LOAD 50,000 FOR THE TANKLESS WATER HEATER
 SEEMS LOW PLEASE CLARIFY. PER (W.P.B.) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS, SECTION 106.1.2
 ADDITIONAL DATA AND FBC FUEL GAS SECTION 401.1 SCOPE.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THIS INCLUDES THE EXISTING MAIN HOUSE GAS
 SYSTEMS LONGEST LENGTH AS WELL AS THE PROPOSED GUEST
 HOUSE WORK. ALSO IF THE GAS SYSTEM IS NATURAL GAS
 PLEASE CORRECT THE INDICATED FUEL GAS TABLE TO BE
 402.4(2).
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 TANKLESS WATER HEATER AND DRYER PER FBC-2004 FUEL GAS
 CODE SECTION 304.
  
 6. CLEARLY INDICATE THE DELIVERY PRESSURE (PSI OR WC)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2. NATURAL GAS
 SPECIFY .5 PSI OR 2 PSI. UNDILUTED PROPANE (LP) 11 INCH
 WC, 2 PSI OR 10 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR THE TANKLESS WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
 *NOTE: THE MANUFACTURER'S SPECIFICATION SHEET AT A
 MINIMUM SHALL CLEARLY INDICATE THE MAKE, MODEL NUMBER,
 BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (THIRD PARTY LISTING).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]