| 2008-04-15 10:01:00 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW ON SHEET A7.1 GAS PIPING ISOMETRIC TO |
| | MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | *NOTE: NOT ALL CUT SECTIONS OF PIPE ARE INDICATING |
| | CORRESPONDING LENGTHS. PLEASE REFERENCE THE RED CIRCLED |
| | YELLOW HIGH LIGHTED CUT SECTIONS THAT REQUIRE |
| | CORRESPONDING LENGTHS. PER FBC FUEL GAS SECTION 401.1 |
| | SCOPE. |
| | |
| | 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| | BEING USED. PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | *NOTE: BTU LOAD 50,000 FOR THE TANKLESS WATER HEATER |
| | SEEMS LOW PLEASE CLARIFY. PER (W.P.B.) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS, SECTION 106.1.2 |
| | ADDITIONAL DATA AND FBC FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: THIS INCLUDES THE EXISTING MAIN HOUSE GAS |
| | SYSTEMS LONGEST LENGTH AS WELL AS THE PROPOSED GUEST |
| | HOUSE WORK. ALSO IF THE GAS SYSTEM IS NATURAL GAS |
| | PLEASE CORRECT THE INDICATED FUEL GAS TABLE TO BE |
| | 402.4(2). |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | TANKLESS WATER HEATER AND DRYER PER FBC-2004 FUEL GAS |
| | CODE SECTION 304. |
| | |
| | 6. CLEARLY INDICATE THE DELIVERY PRESSURE (PSI OR WC) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. NATURAL GAS |
| | SPECIFY .5 PSI OR 2 PSI. UNDILUTED PROPANE (LP) 11 INCH |
| | WC, 2 PSI OR 10 PSI. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR THE TANKLESS WATER |
| | HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. |
| | *NOTE: THE MANUFACTURER'S SPECIFICATION SHEET AT A |
| | MINIMUM SHALL CLEARLY INDICATE THE MAKE, MODEL NUMBER, |
| | BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY (THIRD PARTY LISTING). |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |