Plan Review Notes
Plan Review Notes For Permit 08040117
Permit Number 08040117
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-10 09:42:31 
  
 NONCOMPLIANT
  
 AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 PER 210.70(2)(B) FOR DWELLING UNITS, ATTACHED GARAGES,
 AND DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE
 WALL SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE
 INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR SIDE
 OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS.
 A VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS
 AN OUTDOOR ENTRANCE OR EXIT. LOCATE SAME ON THE PLANS
 WHERE DOORS ARE BEING ADDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718