2008-04-08 13:51:352004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) A NOTICE OF COMMENCEMENT WILL BE REQUIRED.
  
 2) THE VALUE OF THE WORK IS TOO LOW. THE VALUE INCLUDES
 COST OF MATERIALS AS WELL AS LABOR AS WOULD BE CHARGED
 BY A CONTRACTOR. THE VALUE OF THE WORK HAS BEEN
 ADJUSTED TO $ 5595.00 BASED ON MARSHALL AND SWIFT
 ESTIMATING GUIDE. ADDITIONAL FEES OF $ 52.02 ARE DUE.
  
 3) SPECIFY THE TYPE OF WINDOWS AT EACH LOCATION.
 PRODUCT APPROVALS WERE SUBMITTED FOR SINGLE HUNG AND
 FIXED WINDOWS. FBC 106.1.1* CITY AMENDMENTS
  
 4) INDICATE THE LOCATIONS OF THE BEDROOMS ON THE FLOOR
 PLAN AND SHOW THAT THE EGRESS WINDOWS IN THOSE ROOMS
 HAVE NOT BEEN MADE ANY LESS SAFE BY REDUCING THE CLEAR
 OPENING SIZE. 2004 FBC EXISTING BUILDING SECTION
 501.2.
  
  
 5)OPENING #6 FOR THE NEW SLIDING GLASS DOOR IS
 SPECIFIED AS BEING WIDENED MORE THAN DOUBLE THE
 EXISTING OPENING SIZE. THIS DOES NOT CONCUR WITH THE
 PROCEDURES, WHICH SPECIFIES REMOVING THE BLOCK BELOW
 THE SILL. SUBMIT DRAWINGS THAT PROVIDE STRUCTURAL
 DETAILS OF THE NEW OPENING. FBC 106.1.1* CITY
 AMENDMENTS
  
 6) BASED ON THE DIMENSIONS SUBMITTED THE OPENING HEIGHT
 FOR THE DOUBLE DOOR WILL NEED TO BE BUILT DOWN TO
 ACCOMMODATE THE DOORS. PROVIDE STRUCTURAL DETAILS. FBC
 106.1.1* CITY AMENDMENTS
  
 7) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL
 MULLIONS. DCA RULE 9B-72.
  
 8) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 PGT SLIDING GLASS DOOR ARE EXPIRED. SUBMIT CURRENT
 PRODUCT APPROVALS. DCA RULE 9B-72.
  