| Plan Review Notes For Permit 08040103 |
| Permit Number |
08040103 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-09-29 14:54:02 | PLANS ROUTED TO ZONING AS THERE ARE NEW SITE PLANS IN | | | BOTH SETS. | | 2008-09-29 14:53:42 | | | | ** DENIED ** | | | | | | 1) NOTE: THE ELECTRICAL RISER HAS NOW BEEN COMPLETELY | | | REVISED WHICH HAS CREATED NEW COMMENTS WHICH COULD HAVE | | | BEEN MADE ON PREVIOUS REVIEW. | | | PLEASE SEE THE PANEL *B* AT MAIN HOUSE IS MISSING A | | | MAIN DISCONNECTING MEANS PER 225.31-225.39. THE | | | PREVIOUS RISER HAD THIS AS A MAIN CIRCUIT BREAKER | | | PANEL. EVEN IF THERE IS OVER CURRENT PROTECTION AT THE | | | GARAGE A DISCONNECTING MEANS IS REQUIRED AT THE MAIN | | | HOUSE PER SECTIONS OF CODE GIVEN ABOVE. | | | THEY CAN BE FOUND IN THE 2005 NFPA-70 (NEC). | | | | | | 2) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING | | | ELECTRODE SYSTEM REQUIRED AT MAIN HOUSE. THIS IS NOW | | | THE NEW DETACHED BUILDING. NEW FOOTER STEEL IS REQUIRED | | | WHICH WAS ON PREVIOUS PLANS ISSUED FOR PERMIT, COLD | | | WATER PIPE (WHEN METALLIC) AND ANY MADE ELECTRODES AS | | | LISTED. NO GROUNDING ELECTRODE SYSTEM IS SHOWN AT MAIN | | | HOUSE. | | | | | | 3) NOTE: PLEASE INDICATE THE AIC RATING FOR NEW | | | METER/MAIN. 110.9 | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO | | | CONTACT THIS OFFICE. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|