| 2008-09-16 15:28:08 | |
| | ** DENIED REVIEW OF REVISIONS** |
| | |
| | 1) NOTE: PLEASE COORDINATE RISER AND PANELS. THE |
| | FOLLOWING ARE SOME EXAMPLES: |
| | |
| | PANEL *A* SHOWS A 40AMP FEED AND #8 CONDUCTORS TO SUB |
| | PANEL *B* YET THE RISER SHOWS SUB PANELS *B* WITH A |
| | 30AMP MAIN AND #6 CONDUCTORS. |
| | PLEASE SEE CONDUIT SIZE ON THE PANEL *A* SHOWS A 1INCH |
| | CONDUIT WHEN THE RISER SHOWS 3/4INCH. |
| | PLEASE SEE THE RISER STILL INDICATE *OVERHEAD SVC*. |
| | PLEASE SEE NOTE ON RISER WHICH POINTS TO PIE FROM METER |
| | TO THE MAIN PANEL *A* AS FPL SERVICE. THIS CONDUIT |
| | AFTER ANY METERING EQUIPMENT DOES NOT BELONG TO FPL. IN |
| | FACT THE METER CAN AND ANYTHING ON THE LOAD SIDE OF THE |
| | METER CAN IS HOMEOWNER SERVICE. |
| | PLEASE COORDINATE ALL OF THE ABOVE. |
| | 230.2,230.70,230.71, 240.4, 310.16, TABLE 9 ETC |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | ** PLEASE KNOW IT HAS COME TO THE ATTENTION OF THIS |
| | OFFICE THAT POOL EQUIPMENT WILL BE MOVING UP TO MAIN |
| | HOUSE. AS THIS AFFECT NOT ONLY THE LAYOUT OF PLANS, IT |
| | MAY CERTAINLY AFFECT HOW THE ELECTRICIAN WILL FEED |
| | EQUIPMENT. IT JUST MAY NOT BE FED FROM THE PANEL *B* |
| | WHICH IS AT THE GARAGE. |
| | |
| | **PLANS ROUTED BACK TO THE BUILDIGN REVIEWER AT THE |
| | OWNER'S REQUEST. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |