| Plan Review Notes For Permit 08040103 |
| Permit Number |
08040103 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-06-12 16:35:39 | ** REDLINED PLANS ** | | | | | | 1) NOTE: RESPONSE FOR OWNER BUILDER COMMENT AS THIS | | | DOES NOT APPEAR TO BE PRIMARY RESIDENCE MENTIONS THE | | | PROJECT WILL CHANGE TO CONTRACTOR HOWEVER NO CHANGE OF | | | CONTRACTOR WAS SUBMITTED OR PERMIT APPLICATION FOR NEW | | | CONTRACTOR WAS SUBMITTED. | | | PLEASE SEE FS 489 AS THIS RESIDENCE IS REQUIRED TO BE | | | FOR THE OWN USE AND OCCUPANCY OF THE OWNER BUILDER. | | | THIS MAY BE VERIFIED BY THE LICENSING BOARD AND PALM | | | BEACH COUNTY. | | | | | | 2) NOTE: GARAGE PANEL IS SHOWN AS EXISTING AND IS NOT | | | IN SCOPE OF WORK. THE PANEL SHALL BE VERIFIED TO MEET | | | 225.31-225.39, 250.32 AND 250.50 AS NEW FUTURE | | | ELECTRICAL WILL BE GETTING FED FROM THIS EQUIPMENT. | | | THE PERMIT FOR THE SWIMMING POOL WAS ALREADY APPLIED | | | FOR AND PLANS DO NOT COORDINATE FOR BOTH APPLIED. | | | | | | 3) NOTE: PANEL SCHEDULE ONLY LIST ARC FAULT PROTECTION | | | FOR RECEPTACLES. CODE SECTION210.12 OF THE 2005 NEC | | | REQUIRED THE PROTECTION OF ALL OUTLETS IN DWELLING UNIT | | | SLEEPING ROOMS. | | | | | | IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | 2008-06-03 18:57:06 | 2008-06-03 18:57:06 | | | | | | SENT TOLUIS MARTINEZ TO ROUTE TO OTHER TRADES FIRST. | | | ROUTE BACK TO ELEC WHEN OTHERS ARE DONE. |
|