| Plan Review Notes For Permit 08040103 |
| Permit Number |
08040103 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-06-17 15:51:41 | | | | | | | DENIED | | | | | | 1)CHOOSE THE INSTALLATION METHOD FOR THE TPO ROOF | | | MEMBRANE FROM CHOICES ON PAGES 5 & 6 OF THE PRODUCT | | | APPROVAL, PROVIDE SIGNED AND SEALED CALCULATIONS FOR | | | THE CHOSEN METHOD AS REQUIRED BY LIMITATION #7 ON PAGE | | | 7 FOR THE ENHANCED FASTENING FOR PERIMETER AND CORNER | | | ROOF ZONES. PLEASE NOTE THAT ROOF DECK ATTACHMENT PER | | | THE PRODUCT APPROVAL REQUIRES #8 SCREWS AT 6" O/C. | | | | | | 2)THE CHANGE OF CONTRACTOR REQUIRES A FEE AND A NEW | | | PERMIT APPLICATION TO BE FILLED OUT, PLEASE NOTE THAT | | | ALL SUB CONTRACTORS CAN BE LISTED ON THE NEW PERMIT OR | | | THEY CAN PULL THEIR OWN PERMITS SEPARATELY | | | | | | 3)A NEW NOC WILL NEED TO BE RECORDED WITH NEW | | | CONTRACTOR LISTED, THE NOC PROVIDED WAS RECORDED WITH | | | THE OWNER AS THE CONTRACTOR | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|