Plan Review Notes
Plan Review Notes For Permit 08040103
Permit Number 08040103
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-14 11:33:54PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE CLARIFY THE SCOPE OF WORK. THE PERMIT
 APPLICATION INDICATES "ADDITION TO EXISTING HOME",
 HOWEVER SHEET E-1.0 IS INDICATING A GAS GENERATOR BY
 THE EXISTING GAS WATER HEATER WITH NO INFORMATION. IF
 IT IS THE INTENT TO HAVE THE GENERATOR IN THE SCOPE OF
 WORK, PLEASE CLEARLY INDICATE THIS AND COMPLETE THE
 PLANS ACCORDINGLY AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS/CUT SHEETS ON THE GENERATOR CLEARLY
 INDICATING THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY,
 AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY AS WELL AS THE FOLLOWING INFORMATION FOR THE
 GAS SYSTEM (OR DELETE THE GENERATOR FROM PLANS).
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 C. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (THIS INCLUDES THE EXISTING GAS SYSTEM)
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (THIS INCLUDES THE
 EXISTING GAS SYSTEM)
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 LP GAS SPECIFY .5 PSI, 2 PSI OR 10 PSI .
  
 2. SITE PLAN ARCHITECTURAL NOTES, PLUMBING GENERAL
 NOTES (7): AIR CHAMBERS ARE NOT APPROVED BY THE FBC
 PLUMBING SECTION 604.9 WATER HAMMER. HOWEVER IF IT IS
 THE INTENT TO USE AIR CHAMBERS THEY SHALL BE INSTALLED
 PER "STANDARD PDI-WH 201" WITH A RECHARGABLE TYPE OF
 AIR CHAMBER (DETAIL REQUIRED) OR DELETE AIR CHAMBERS
 FROM PLANS.
  
 3. SHEET A-3.0 ROOF PLAN ROOF DRAINAGE CALCULATIONS
 APPEAR TO BE WRONG FOR EACHROOF AREA. AREA #1 & #2 ONLY
 HAVE 48 SQUARE INCHES OF PROVIDED SCUPPER. AREA #3
 SHOULD NOT HAVE ANY SCUPPERS. SQUARE FOOTAGE FOR AREA
 #2 APPEARS WAY TO LOW, THIS ROOF AREA IS RECIEVING ALOT
 MORE THAN THE INDICATED 207 SQ. FT. PLEASE CLEARLY
 IDENTIFY EACH SCUPPER WITH INDIVIDUAL SQUARE FOOTAGE
 AND VERTICAL WALL CALCULATIONS FOR EACH SCUPPER. PER
 FBC PLUMBING SECTION1101.1 SCOPE, 1101.7 ROOF DESIGN,
 AND 1106.4 VERTICAL WALLS.
  
 4. SHEET A-3.0 ROOF PLAN: PLEASE CLEARLY IDENTIFY ALL
 "UNDERCUT PARAPET FOR DRAINAGE", ONE IS NOT IDENTIFIED
 FROM AREA 1 TO AREA 2. PER FBC PLUMBING SECTION 1101.1
 SCOPE.
  
 5. SHEET A-3.0 ROOF PLAN: SECONDARY ROOF DRAINAGE IS
 REQUIRED. PER FBC PLUMBING SECTION 1107.1 SECONDARY
 DRAINAGE REQUIRED. THE SECONDARY ROOF DRAINAGE SYSTEM
 SHALL BE SEPERATE FROM THE PRIMARY ROOF DRAINAGE
 SYSTEM. PER FBC PLUMBING SECTION 1107.2 SEPERATE
 SYSTEMS REQUIRED.
  
 6. SHEET A-3.0 ROOF PLAN: DRAINAGE FOR THE SCUPPERS
 SHALL DRAIN A MINIMUM OF 1 FOOT AWAY FROM BUILDING
 STRUCTURE. PER FBC BUILDING SECTION 1503.6 PROTECTION
 AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 7. SHEET S-1.0 PART. PLUMBING RISER UTILITY: CLEARLY
 IDENTIFY THE TRAP FOR THE WASHING MACHINE AS BEING 2
 INCH. PER FBC PLUMBING SECTION 406.3 WASTE CONNECTION.
 A 3 INCH CLEANOUT IS REQUIRED FOR THE WASHING MACHINE
 DRAINAGE STACK PER FBC PLUMBING SECTION 708.7 MINIMUM
 SIZE. THE CLEANOUT SHALL BE LOCATED AT 4 FEET ABOVE
 FINNISH FLOOR. PER FBC PLUMBING SECTION 708.9 ACCESS.
  
 8. SHEET S-1.0 PLUMBING RISER DIAGRAM: A TWO-WAY
 CLEANOUT SHALL BE LOCATED AT THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PLUMBING
 SECTION 708.3.5 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]