2008-04-08 16:22:54** DENIED REVIEW**
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON ELECTRICAL PLANS.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 FBC 106.1.2, 106.3.5, FS 553.73 FOR INFORMATION
 REQUIRED ON PLANS.
  
 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS PLANS SHOW
 SMOKE DETECTION DEVICES AS *SMOKE DETECTORS*. SMOKE
 DETECTORS ARE DEVICES WHICH ONLY DETECT AND DO NOT
 SOUND AN ALARM. PLEASE SEE NFPA72 AS * SMOKE ALARMS ARE
 DEVICES WHICH DETECT AND SOUND AN ALARM. IF THESE ARE
 SMOKE DETECTORS PLEASE INCLUDE THE REMAINDER OF THE
 SYSTEM SUCH AS HORN DEVICES, FIRE ALARM PANEL ETC. IF
 THESE ARE DEVICES WHICH ARE INDEED DEVICES WHICH DETECT
 AND SOUND AN ALARM PLEASE ADJUST DESIGNATIONS. PLEASE
 SEE THE NEXT COMMENT FOR ALL LOCATIONS.
  
 3) NOTE: PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1,
 11.8.3 AS THE EXISTING DWELLING SHALL ALSO CONTAIN
 HARDWIRED DEVICES BEING BROUGHT UP TO THE CURRENT
 NFPA-72.
 PLEASE SHOW ALL LOCATIONS MEETING EXISTING MEETING CODE
 OR NEW TO BE INSTALLED.
  
 4) NOTE: PLEASE VERIFY THE SCOPE OF WORK AS APPLIED AND
 SHOWN ON PLANS. FOR EXAMPLE: ELECTRICAL PLANS SHOWS GAS
 GENERATOR, AND OTHER ITEMS WHICH NO INFORMATION,
 ELECTRICAL OR OTHER WISE WAS SUBMITTED. IF THE
 GENERATOR IS TO BE IN THE SCOPE OF WORK, PLEASE
 COMPLETE PLANS ACCORDINGLY AND SUBMIT MANUFACTURES
 SPECS/CUT SHEETS ON NEW TRANSFER SWITCH AND GENERATOR.
 PLEASE ADJUST RISER, SITE PLANS, ETC.
 AS THE PLANS ARE NOT COMPLETE FOR THESE OTHER ITEMS, NO
 REVIEW OF THESE ITEMS COULD BE DONE AT THIS TIME.
 110.3, 90.7, 702.5, 240.4, 310.16 ETC.
 FBC 106.3.5.4, 106.1.2 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE MISSING INFORMATION ON REQUIRED
 FEED TO GARAGE WITH FEEDERS, LIGHTS, GFI ETC.
 PLEASE SEE NEC 2005. 310.16, 215.5, 250.32,
 225.31-225.39, 210.8A, 210.52G ETC
 THE LOAD SCHEDULE NOW SHOWS ALL CIRCUITS TO DETACHED
 BUILDING AND EQUIPMENT AS SEPARATE FEEDS HOWEVER THIS
 DOES NOT COMPLY WITH THE MINIMUM REQUIRED PER
 225.31-225.39 AND 250.32, 250.50.
  
 6) NOTE: PLEASE BE SURE TO SHOW THE LOCATION OF THE CU
 ON ELECTRICAL PLANS INCLUDING DISCONNECT PER 440.11.
 THE ELECTRICAL PLANS APPEAR TO SHOW SOME SORT OF
 DISCONNECT HOWEVER THE LOCATION OUTSIDE THE BATHROOM
 DOES NOT COORDINATE WITH THE MECHANICAL PLANS
 SUBMITTED.
 210.63, 210.8A, 440.11
  
 7) NOTE: PLEASE SUBMIT A PANEL SCHEDULE SHOWING ALL
 MINIMUM AND OTHER BRANCH CIRCUITS PER 408.4, 310.16,
 240.4.
 FBC 106.1.2, 106.3.5.4
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE SPACING IN NEW
 BEDROOM REQUIRED WITHIN 6FT OF DOOR PER 210.52.
  
 9) NOTE: PLEASE SEE 210.52D AS THE REQUIRED GFI IN NEW
 BATH SHALL BE WITHIN 3FT OF SINK/LAVATORY EDGE. THIS
 DOES NOT PERMIT CROSSING OVER OF SINK TO GAIN ACCESS TO
 GFI RECEPTACLE.
 PLEASE RELOCATE OR ADD ADDITIONAL GFI.
  
 10) NOTE: PLEASE SEE 210.8A7 AS ALL 15/20AMP 120V
 RECEPTACLES WITHIN 6FT OF LAUNDRY SINK SHALL BE GFI/GFI
 PROTECTED. THIS INCLUDES DEDICATED CIRCUITS SUCH AS
 WASHER. THIS WAS A CHANGE IN THE 2005 NEC.
  
 11) NOTE: PLEASE SEE 210.11C2, 220.52B AS THE LAUNDRY
 AND WASHER LOADS SHALL BE 1500VA MIN.
  
 12) NOTE: PLEASE SEE THE LOAD SCHEDULE SHOWS ONLY ONE
 CIRCUIT AS *EXISTING* AND IF OTHER CIRCUITS ARE NOT
 SHOWN AS *EXISTING* IT WOULD AUTOMATICALLY BE *NEW*
 HOWEVER THE ELECTRICAL PLANS DO NOT ANY OTHER
 ELECTRICAL ITEMS SUCH AS KITCHEN ETC AS NEW?
 PLANS ARE NOT CLEAR WITH COMPLETE SCOPE OF WORK.
  
 13) NOTE: NOTE FOR INFORMATIONAL PURPOSE TO
 OWNER/BUILDER APPLICANT.FS 489 REQUIRES LOCATION TO
 BE OWNER OCCUPIED FOR OWN USE AND OCCUPANCY. PALM BEACH
 COUNTY PROPERTY APPRAISER OFFICE INDICATES MULTIPLE
 PROPERTIES INCLUDING SEPARATE PROPERTY AS HOMESTEAD.
 THIS WAS NOTED FOR INFORMATIONAL PURPOSE ONLY AS
 APPLICANT MUST USE THIS LOCATION FOR OWN USE AND
 OCCUPANCY.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  