| 2008-04-17 09:06:13 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT L-2 INDICATES IRRIGATION WORK. NO IRRIGATION |
| | WORK IS INDICATED ON THE PERMIT APPLICATION. PLEASE |
| | INDICATE THE EXTENT OF THE INTENDED IRRIGATION WORK. |
| | WILL THIS BE A NEW SYSTEM? WILL THE SYSTEM, IF |
| | EXISTING, BE ENLARGED, ALTERED, MOVED OR DEMO'D? PLEASE |
| | CLARIFY. IF THE SYSTEM IS NEW, PLEASE SHOW THE LOCATION |
| | OF THE WATER SOURCE, (METER OR WELL), THE BACKFLOW |
| | PREVENTER IF CITY WATER, THE CONTROLLER & THE RAIN |
| | SENSOR. SECTIONS 105.1, 106.1.1, 106.1.2, 608 & FS |
| | 373.62. |
| | |
| | 2. SHT A1.0 BOTH TOILET ROOMS SHALL BE ACCESSIBLE. |
| | PLEASE SHOW COMPLIANCE WITH SECTIONS 1104.16, 11-4.19 & |
| | 11-4.22 WITH ALL SUBSECTIONS FOR BOTH TOILET ROOMS. |
| | SECTION 11-4.1.6(1)(B). (DOOR SHALL NOT SWING OPEN INTO |
| | THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SECTION |
| | 11-4.22.2(1). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |