| 2008-04-09 10:40:33 | ** DENIED REVIEW** |
| | |
| | ** PLEASE SEE SOME NOTES UNDER PREVIOUS EXPIRED PERMIT |
| | APPLICATION WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| | ARE STATED ON ELECTRICAL PLANS. |
| | FBC 2004 W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | FBC 106.1.2, 106.3.5, FS 553.73 |
| | FOR INFORMATION REQUIRED ON PLANS. SOME CODES MAY |
| | ALREADY BE ON PLANS BUT NOT ALL. |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE FOR THE SCOPE OF WORK IS |
| | TOO LOW. THE VALUE SHALL INCLUDE ALL EQUIPMENT, LABOR |
| | AND MATERIALS. FBC 108.3. |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR ALL INTERIOR |
| | ELECTRICAL FOR NEW EQUIPMENT LIGHTING ETC. THE SCOPE OF |
| | WORK FOR EQUIPMENT ETC WILL NEED ELECTRICAL TO BE |
| | SHOWN. |
| | |
| | 2) NOTE: PLEASE SEE PLANS NEED TO COMPLY WITH FBC |
| | CHAPTER 13, 13-415.2, 13-415.2.ABC.1.1, .1. AND .1.3. |
| | PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE |
| | CALCULATIONS. |
| | |
| | 3) NOTE: PLEASE SEE 210.8B2 AS GFI/GFI PROTECTION IS |
| | REQUIRED FOR ALL 15/20AMP 120VRECEPTACLES. |
| | PLEASE LIST/SHOW ALL CIRCUITS. |
| | |
| | 4) NOTE:PLEASE SEE 700.12F FOR ANY EMERGENCY AND EXIT |
| | LIGHTS SHALL BE CIRCUITED TO LOCAL BRANCH CIRCUIT. |
| | |
| | 5) NOTE: IF THE SCOPE OF WORK IS THAT OF OTHER RECENT |
| | KFC REMODELS FOR KITCHENS ETC, PLANS WILL NEED TO SHOW |
| | PANELS, LOADS, CIRCUITING ETC. |
| | ***PLEASE KEEP THIS IN MIND. |
| | |
| | 6) NOTE: PLEASE SUBMIT TWO COMPLETE SETS FOR NEW SCOPE |
| | OF WORK.THREE SETS WERE SUBMITTED HOWEVER TWO OF |
| | THOSE WERE OLD WITH VOID STAMPS. |
| | 106.1 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |