| 2008-04-23 07:34:42 | BUILDING PLAN REVIEW |
| | PERMIT: 08040097 |
| | ADD: 4720 N BROADWAY |
| | CONT: NUNNO BUILDERS |
| | TEL: (954)961-0777 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS PLEASE |
| | CORRECT THE PLANS NOW INDICATE THE 2006 SUPPLEMENTS. |
| | |
| | 1F) PLANS FAIL TO MENTION THE DESIGN REQUIREMENTS OF |
| | THE EXISTING BUILD |
| | ING CODE, 2004 WITH 2007 SUPPLEMENTS. |
| | |
| | 1G) PLANS INDICATE THIS TO BE A TYPE III BUILDING. THE |
| | RESPONSE SHEET INDICATES THE PLAN WAS CHANGED TO A V-B, |
| | BUT THEY CLEARLY STATE TYPE III BUT DO NOT INDICATE A |
| | OR B? TABLE 503, TABLE 601. |
| | |
| | 1H)PLANS ALSO INDICATE THIS TO BE A LEVEL I |
| | ALTERATION. PLEASE SEE THE EXISTING BUILDING CODE |
| | SECTION 305, LEVEL 3 APPLY WHERE THE WORK AREA EXCEEDS |
| | 50 PER CENT OF THE AGGREGATE AREA OF THE BUILDING AND |
| | MADE WITHIN ANY 12-MONTH PERIOD. |
| | |
| | 2) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF |
| | PRODUCT |
| | TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS: A) |
| | EFIS WALL SYSTEMS MISSING THE FLORIDA COVER SHEET/ |
| | DESIGNER OF RECORD APPROVAL |
| | WITH SHOP DRAWING STAMP IS REQUIRED, 2 SETS OF |
| | PRODUCT APPROVALS ONLY ONE SUBMITTED. |
| | |
| | B) TRUSS ANCHORS NONE SUBMITTED WILL REQUIRE THE |
| | FLORIDA COVER SHEET/ DESIGNER OF |
| | RECORD APPROVALWITH SHOP DRAWING STAMP. |
| | |
| | C) ROOFING ASSEMBLIES- NONE SUBMITTED,THE FLORIDA |
| | COVER SHEET/ DESIGNER OF RECORD APPROVAL |
| | WITH SHOP DRAWING STAMP. SUBSYSTEMS ARE NOT |
| | HIGHLIGHTED. WILL REQUIRE ENHANCED |
| | FASTENING IN ZONES 2 & 3. PROVIDE RAS 117 |
| | CALCULATIONS PER LIMITATION# 7. |
| | |
| | D) FIXED/ STOREFRONT WINDOWS-NONE WERE SUPPLIED. |
| | PROVIDETHE FLORIDA COVER SHEET/ PRODUCT TESTING |
| | SHEETS & DESIGNER OF RECORD APPROVALWITH SHOP DRAWING |
| | STAMP. |
| | |
| | |
| | 3)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT |
| | APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5A) 2ND REQUEST, SHEET A-4.1 INDICATES THE FRAMING |
| | DETAIL FOR THE NEWLY DESIGNEDTOWER, SHEET A-4.1 |
| | INDICATES THE NEW TOWER HAS THE CENTER OPEN AND THE |
| | INSIDE WALLS HAVE A MODIFIED BITUMEN ROOFING MEMBRANE, |
| | THERE APPEARS TO BE NO ROOF DRAIN NOR OVERFLOW SCUPPERS |
| | TO ALLOW THE RAIN WATER OUT OF THIS BOX LOOKING TOWER. |
| | HOW WILL RAIN WATER BE DRAINED? |
| | |
| | 5B) SHEET A.4.0, A.4.1 & A5.0 ALL SHOW THE PARAPET |
| | DETAILS, BUT NONE INDICATE HOW THE PARAPET WILL BE |
| | ATTACHED TO THE EXISTING STRUCTURE? 106.1.2*/ 1609 HOW |
| | WILL THE MOMENT OF OVERTURNING BE RESTRICTED? |
| | |
| | 6) NOTE:COMPLIED CANOPY AND AWNINGS TO BE UNDER A |
| | SEPARATE PERMIT.A LETTER FROM THE OWNER (NOT TENANT) |
| | IS TO ACCOMPANY ALLFABRIC OR MEMBRANE-COVERED |
| | STRUCTURE DESIGNED WITH A QUICK REMOVAL OR BREAKAWAY |
| | MEMBRANE OR FABRIC TO ACKNOWLEDGE THEIR RESPONSIBILITY |
| | TO HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND |
| | EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. |
| | THE LETTER MUST BE SIGNED BY THE OWNER NOT TENANT. |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, |
| | |
| | 7)SHEET A-4.1 WALL SECTION D AT CUPOLA,PLEASE |
| | CORRECT NOTATION TO DESIGN OF AWNING TO FBC CHAPTER |
| | 43NOTE TO WHICH DESIGN THIS FABRIC CUPOLA WILL BE |
| | DESIGNED TO, 3105.4.2.1 OR 3105.4.2.2, |
| | |
| | A LETTER FROM THE OWNER (NOT TENANT) IS TO ACCOMPANY |
| | ALLFABRIC OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH |
| | A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO |
| | ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE THE AWNING |
| | COVER REMOVED PRIOR TO ANY WIND EVENT WITH PROJECTED |
| | WIND SPEEDS OF 75 MPH OR GREATER. THE LETTER MUST BE |
| | SIGNED BY THE OWNER NOT TENANT. |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |