Plan Review Notes
Plan Review Notes For Permit 08040089
Permit Number 08040089
Review Stop P
Sequence Number 2
Notes
Date Text
2008-05-05 15:18:52PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS FOR THE PURPOSE
 OF CONTINUITY. NEW COMMENTS WILL BE SO NOTED FOLLOWING
 THE PREVIOUS REVIEW COMMENTS.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM OF THE
 PROPOSED BATHROOM CLEARLY INDICATING THE FIXTURES WITH
 ALL WASTE, VENTS, TRAP SIZES AND CLEANOUT LOCATIONS.
 **THE RESUBMITTED ISOMETRIC IS NOT CODE COMPLIANT AND
 DOES NOT REFLECT THE FLOOR PLAN OF THE PROPOSED
 BATHROOM. PLEASE REFERENCE THE SANITARY ISOMETRIC RISER
 DIAGRAM ATTACHED TO THESE PLUMBING COMMENTS THAT
 REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT. THE
 FOLLOWING ITEMS ARE NOT CODE COMPLIANT ON THE
 RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM.
  
 A} HORIZONTAL DRY VENTS ARE NOT ALLOWED. PLEASE
 REFERENCE THE YELLOW HIGH LIGHTED AREAS INDICATING
 HORIZONTAL DRY VENTS ON THE RESUBMITTED SANITARY
 ISOMETRIC RISER DIAGRAM. PER FBC-2004 PLUMBING SECTION
 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
  
 B} THE TEE FITTING ON THE WASHING MACHINE STANDPIPE
 CONNECTING TO THE 3 INCH VENT IS NOT COMPLIANT DUE TO
 THE FACT IT IS ABOVE THE WATER-SEAL OF THE TRAP AND
 WILL ALLOW SEWER GAS TO ENTER THE ROOM WHERE THE
 WASHING MACHINE IS LOCATED. PLEASE REFERENCE THE RED
 CIRCLED YELLOW HIGH LIGHTED AREA INDICATING THIS
 PROPLEM. PER FBC-2004 PLUMBING SECTION 1002.1 FIXTURE
 TRAPS.
  
 C} FLOOR PLAN IS INDICATING THE SINK FOR THE BATHROOM
 AS EXISTING. HOW IS THIS SINK EXISTING WHEN THE PERMIT
 APPLICATION STATES CONVERT UTILITY ROOM TO BATHROOM?
 THE RESUBMITTED SANITARY ISOMETRIC IS MISSING THE
 LAVATORY FOR THE PROPOSED BATHROOM. PER FBC-2004
 PLUMBING SECTION 701.1 SCOPE.
  
 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]