2008-04-21 11:10:24PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) 2004 FBC/R 303.3 REQUIRES VENTILATION FOR ALL
 BATHROOMS, PLEASE SHOW ON THE PLAN HOW THIS BATHROOM
 WILL BE VENTILATED.
  
 *** 2004 FBC/R R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.279 M 2 ),
 ONE-HALF OF WHICH MUST BE OPENABLE.
  
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A MECHANICAL VENTILATION SYSTEM
 ARE PROVIDED. THE MINIMUM VENTILATION RATES SHALL BE 50
 CFM (23.6 L/S) FOR INTERMITTENT VENTILATION OR 20 CFM
 (9.4 L/S) FOR CONTINUOUS VENTILATION. VENTILATION AIR
 FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTSIDE.
  