| Date |
Text |
| 2008-04-15 11:38:43 | 2004 FBC W/2007 REVISIONS |
| | ADDITION TO GARAGE |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) PROVIDE DETAILS FOR THE ATTACHMENT OF THE BOND BEAM |
| | AND FOOTING REINFORCEMENT TO THE EXISTING STRUCTURE. |
| | FBC 106.1.1* CITY AMENDMENTS |
| | |
| | 3) SPECIFY THE LOCATION OF THE VERTICAL REINFORCEMENT |
| | AT THE CORNERS AND EACH SIDE OF THE DOOR OPENING. FBC |
| | R609.3 |
| | |
| | 4) SPECIFY THE APPLICABLE BUILDING CODE AND WIND DESIGN |
| | INFORMATION ( BASIC WIND SPEED AND EXPOSURE CATEGORY) . |
| | FBC R301 |
| | |
| | 5) A SIMPSON MTS 18 IS SPECIFIED FOR THE RAFTER TO |
| | EXISTING WALL CONNECTION. IF THE EXISTING WALL IS |
| | MASONRY, A DIFFERENT CONNECTOR SHOULD BE USED, SUCH AS, |
| | THE MTSM 16 OR HTSM 16. PLEASE REVIEW. FBC 106.1.1.2* |
| | CITY AMENDMENTS |
| | |
| | 6) THE LAP LENGTH FOR THE #7 BARS SPECIFIED FOR THE |
| | BOND BEAM IS 59" PER FBC TABLE R606.9.2. PLEASE SPECIFY |
| | ON THE PLANS. |
| | |
| | 7) THE ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE |
| | WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC |
| | RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL |
| | BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT |
| | 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT |
| | INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS |
| | SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 |
| | MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH |
| | FIGURE R803.2.3.1. |
| | |
| | 8) THE PRODUCT APPROVALS FOR THE DOUBLE OUTSWING DOOR |
| | DOORS THAT WERE SUBMITTED ARE EXPIRED, EXCEPT FOR THE |
| | ONE FOR THE NON-IMPACT RATED GLAZED DOORS. SUBMIT |
| | CURRENT PRODUCT APPROVALS FOR THE DOOR THAT WILL BE |
| | INSTALLED. DCA RULE 9B-72. |
| | |
| | 10) THE PRODUCT APPROVALS SUBMITTED FOR THE GAF ROOF |
| | COVERING CONTAINS SEVERAL ASSEMBLIES AND DECK TYPES. |
| | SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND |
| | DESIGN PRESSURE THAT WILL BE USED. CIRCLE THE CORRECT |
| | ITEMS FROM THE PRODUCT APPROVAL. ENHANCED FASTENING MAY |
| | BE REQUIRED AT THE PERIMETER AND CORNER AREAS. SEE |
| | LIMITATION #7 AND SUBMIT RAS 117 CALCULATIONS FOR |
| | ENHANCED FASTENING AS REQUIRED BY THE PRODUCT |
| | APPROVAL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |