| 2008-11-18 16:57:08 | |
| | |
| | |
| | ** FAILED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE NOTES BELOW. |
| | |
| | 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS NOT IN |
| | COMPLIANCE WITH FBC 13-415.2,13-415.2.ABC.1.1, .1.2, |
| | .1.3. |
| | NONE SUBMITTED FOR EXTERIOR AS SHOWN ON ARCHITECTURAL |
| | PLANS AS WELL AS THE FIXTURE LEGEND ON THE ELECTRICAL |
| | PLANS. |
| | PLEASE SEE THE INTERIOR CALCULATIONS AS SUBMITTED ARE |
| | ALSO IN QUESTION. THE ALLOWANCES INCLUDING ALL FIXTURE |
| | VA RATINGS NEED COORDINATING. PLEASE SEE FOR EXAMPLE |
| | THE ELIPTIPAR FIXTURE PER THE MANUFACTURE WEBSITE |
| | CONTAINS 2-28W BULBS PER FIXTURE. THIS WOULD BE A TOTAL |
| | OF 56 VA PER FIXTURE AND PLANS SHOW A TOTAL OF TWO OF |
| | THESE FIXTURES. HOWEVER THE PLANS SHOW A TOTAL WATTAGE |
| | OF 56 FOR BOTH. THIS IS NOT POSSIBLE. |
| | |
| | ** PLEASE GO OVER ALL LIGHTING AND LIGHTING |
| | CALCULATIONS. BASED ON THE PLANS SUBMITTED THE DESIGN |
| | WATTAGES AS SUBMITTED AND SHOWN IS OVER THE ALLOWANCE |
| | PER THE FLORIDA BUILDING CODE SECTIONS AS GIVEN ABOVE. |
| | AS NO LIGHTING CALCULATIONS WERE SUBMITTED FOR REVIEW |
| | ONCE AGAIN FOR THE EXTERIOR LIGHTING, NO REVIEW FOR |
| | CODE COMPLIANCE OF THOSE ITEMS COULD BE DONE. |
| | PLEASE CALL TO GO OVER ANY OF THESE. |
| | |
| | 2) NOTE: PLEASE SEE FS 553.80(2)(B). AS A STATUTORY |
| | REQUIREMENT WHEN PLANS HAVE REPEAT COMMENTS FOR CODE |
| | COMPLIANCE WITH THE SAME SPECIFIC CODE SECTION GIVEN |
| | THREE OR MORE TIMES. THE STATUTE AS STATED REQUIRES A |
| | 4X FEE FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT |
| | FEE TO BE ASSESSED. THIS FEE IS NOT AN OPTIONAL FEE OF |
| | THE BUILDING OFFICIAL TO BE ASSESSED, IT IS A REQUIRED. |
| | THE BASE PERMIT FEE NOT INCLUDING FIRE REVIEW, TRAINING |
| | SURCHARGE FEE ETC IS $1,050. THE PLAN REVIEW PORTION OF |
| | THIS BASE FEE IS 30% (PERCENT) TIMES FOUR AS REQUIRED |
| | PER SECTION OF STATUTE GIVEN. THIS IS $315.00 TIMES |
| | FOUR WHICH IS $1,250. |
| | |
| | ** THE 10 PERCENT RE-SUBMITTAL FEE WILL NOT BE |
| | REQUIRED. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |