Plan Review Notes
Plan Review Notes For Permit 08040069
Permit Number 08040069
Review Stop E
Sequence Number 3
Notes
Date Text
2008-11-18 16:57:08 
  
  
 ** FAILED 3RD REVIEW **
  
 ** PLEASE SEE NOTES BELOW.
  
 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS NOT IN
 COMPLIANCE WITH FBC 13-415.2,13-415.2.ABC.1.1, .1.2,
 .1.3.
 NONE SUBMITTED FOR EXTERIOR AS SHOWN ON ARCHITECTURAL
 PLANS AS WELL AS THE FIXTURE LEGEND ON THE ELECTRICAL
 PLANS.
 PLEASE SEE THE INTERIOR CALCULATIONS AS SUBMITTED ARE
 ALSO IN QUESTION. THE ALLOWANCES INCLUDING ALL FIXTURE
 VA RATINGS NEED COORDINATING. PLEASE SEE FOR EXAMPLE
 THE ELIPTIPAR FIXTURE PER THE MANUFACTURE WEBSITE
 CONTAINS 2-28W BULBS PER FIXTURE. THIS WOULD BE A TOTAL
 OF 56 VA PER FIXTURE AND PLANS SHOW A TOTAL OF TWO OF
 THESE FIXTURES. HOWEVER THE PLANS SHOW A TOTAL WATTAGE
 OF 56 FOR BOTH. THIS IS NOT POSSIBLE.
  
 ** PLEASE GO OVER ALL LIGHTING AND LIGHTING
 CALCULATIONS. BASED ON THE PLANS SUBMITTED THE DESIGN
 WATTAGES AS SUBMITTED AND SHOWN IS OVER THE ALLOWANCE
 PER THE FLORIDA BUILDING CODE SECTIONS AS GIVEN ABOVE.
 AS NO LIGHTING CALCULATIONS WERE SUBMITTED FOR REVIEW
 ONCE AGAIN FOR THE EXTERIOR LIGHTING, NO REVIEW FOR
 CODE COMPLIANCE OF THOSE ITEMS COULD BE DONE.
 PLEASE CALL TO GO OVER ANY OF THESE.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B). AS A STATUTORY
 REQUIREMENT WHEN PLANS HAVE REPEAT COMMENTS FOR CODE
 COMPLIANCE WITH THE SAME SPECIFIC CODE SECTION GIVEN
 THREE OR MORE TIMES. THE STATUTE AS STATED REQUIRES A
 4X FEE FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT
 FEE TO BE ASSESSED. THIS FEE IS NOT AN OPTIONAL FEE OF
 THE BUILDING OFFICIAL TO BE ASSESSED, IT IS A REQUIRED.
 THE BASE PERMIT FEE NOT INCLUDING FIRE REVIEW, TRAINING
 SURCHARGE FEE ETC IS $1,050. THE PLAN REVIEW PORTION OF
 THIS BASE FEE IS 30% (PERCENT) TIMES FOUR AS REQUIRED
 PER SECTION OF STATUTE GIVEN. THIS IS $315.00 TIMES
 FOUR WHICH IS $1,250.
  
 ** THE 10 PERCENT RE-SUBMITTAL FEE WILL NOT BE
 REQUIRED.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  