2008-07-03 15:30:04***DENIED***
  
  
 NO COMMENTS WERE ADDRESSED FROM FIRST FIRE REVIEW. THE
 FOLLOWING COMMENTS ARE TAKEN DIRECTLY FROM THAT
 REVIEW:
  
 1) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241. ADD NFPA 241TO
 APPLICABLE CODES ON SHEET A-0.
  
 2) ON SHEET A-0 UNDER THE APPLICABLE CODES, BE ADVISED
 THAT NFPA 72 IS A FIRE ALARM CODE. UNDER TYPE, CHANGE
 FROM FIRE PREVENTION TO FIRE ALARM.
  
 3) SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE STRUCTURE
 OF EXTERIOR ELEVATION WHICH FRONTS NORTH DIXIE HIGHWAY.
 AS PER WEST PALM BEACH REQUIREMENTS, THE NUMBERS SHALL
 BE NOT LESS THAN 6" IN HEIGHT, 1" IN WIDTH AND
 CONTRASTING WITH BACKGROUND. PLEASE BE ADVISED THAT
 AWNINGS, SIGNS AND /OR SECURITY SHUTTERS SHALL NOT
 OBSTRUCT VISIBILITY OF THE ADDRESS NUMBERS.
  
 4) ON SHEET A-0 IT IS STATED THAT TWO EXITS ARE
 PROVIDED, HOWEVER ONLY ONE EXIT ON THE NORTH ELEVATION
 IS SHOWN ON A-6/ LIFE SAFETY PLAN SHEET. SHOW THE
 LOCATION OF THE SECOND EXIT.
  
 5) PLEASE EXPLAIN HOW ACCESS IS MADE TO THE RECTANGULAR
 PORTION LOCATED AT THE SOUTHWEST CORNER OF THE
 STRUCTURE BEHIND THE COOLATTA/ESPRESSO STATION.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, IT WOULD BE
 HELPFUL TO PROVIDE A RESPONSE LETTER INDICATING HOW AND
 WHERE ON THE PLANS THE COMMENT WAS ADDRESSED.
  
  
 MICHAEL R. WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE ZPREVENTION (561) 804-4756