| Plan Review Notes For Permit 08040069 |
| Permit Number |
08040069 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-06 14:40:40 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | | NFPA 241 TO APPLICABLE CODES ON SHEET A-0 | | | | | | 2.ON SHEET A-0 UNDER THE APPLICABLE CODES, BE ADVISED | | | THAT NFPA 72 IS A FIRE ALARM CODE.UNDER TYPE CHANGE | | | FROM FIRE PREVENTION TO FIRE ALARM | | | | | | 3.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE STRUCTURE | | | OF EXTERIOR ELEVATION WHICH FRONTS NORTH DIXIE HIGHWAY. | | | AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO | | | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN | | | WIDTH/STROKE.PLEASE BE ADVISED THAT AWNINGS, SIGNS, | | | AND/OR SECURITY SHUTTERS SHALL NOT OBSTRUCT VISIBILITY | | | OF THE ADDRESS NUMBERS. | | | | | | 4.ON SHEET A-0 IT IS STATED THAT TWO EXITS ARE | | | PROVIDED, HOWEVER ONLY ONE EXIT (ON THE NORTH | | | ELEVATION) IS SHOWN ON A-6/LIFE SAFETY PLAN SHEET. SHOW | | | THE LOCATION OF THE SECOND EXIT | | | | | | 5.PLEASE EXPLAIN HOW ACCESS IS MADE TO THE | | | RECTANGULAR PORTION LOCATED AT THE SOUTHWEST CORNER OF | | | THE STRUCTURE BEHIND THE COOLATTA/EXPRESSO STATION. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|