| 2008-04-09 09:03:36 | ** DENIED REVIEW** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| | ARE STATED ON ELECTRICAL PLANS. |
| | FBC 2004 W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | PLEASE SEE COVER SHEET MENTIONS FLORIDA ENERGY CODE PER |
| | CHAPTER 11 AND 13. CHAPTER 11 OF THE FBC IS FOR |
| | ACCESSIBILITY/ ADA. |
| | FBC 106.1.2, 106.3.5, FS 553.73 FOR INFORMATION |
| | REQUIRED ON PLANS. |
| | |
| | 2) NOTE: PLEASE SEE PLANS NEED TO COMPLY WITH FBC |
| | CHAPTER 13, 13-415.2, 13-415.2.ABC.1.1, .1. AND .1.3. |
| | PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE |
| | CALCULATIONS.THE LIGHTING CALCULATIONS SUBMITTED ARE |
| | NOT CODE COMPLIANT AND ARE NOT POSSIBLE AS SHOWN. |
| | FOR EXAMPLE: PLEASE SEE TABLE SHOWS 38-32W FIXTURES. |
| | HOW IS THIS POSSIBLE WHEN SEVERAL FIXTURES ARE 96VA OR |
| | MORE? PLEASE SEE FIXTURES A1, A1PP ETC. |
| | PLEASE SPECIFICALLY SEE SECTION 13-415.2.ABC.1.1 AS |
| | NOTED ABOVE FOR TRACK LIGHTING ALSO. |
| | |
| | ** THE EXAMPLE ABOVE IS ONE EXAMPLE AND IS IN NO WAY |
| | ALL ITEMS WHICH NEED TO BE ADDRESS WITH RESPECT TO |
| | LIGHTING PERFORMANCE CALCULATIONS AND IS NOT AN |
| | EXHAUSTED LIST. |
| | |
| | 3) NOTE: PLEASE SEE 210.8B2 AS GFI/GFI PROTECTION IS |
| | REQUIRED FOR ALL 15/20AMP 120VRECEPTACLES. |
| | PLEASE LIST/SHOW ALL CIRCUITS. |
| | |
| | 4) NOTE: PLEASE VERIFY SERVICE AS THE PANELS ARE |
| | SHOWING THESE AS 5-PHASE BASED ON PANELS SHOWN ON RISER |
| | DIAGRAM. THIS IS NOT POSSIBLE AND MUST BE SOME SORT OF |
| | MIS-PRINT. |
| | PLEASE ALSO CLARIFY OTHER DESIGNATIONS SHOWN ON THE |
| | PANELS ON RISER. |
| | |
| | 5) NOTE: PLEASE KNOW THAT AN APPLICATION WAS MADE FOR |
| | SIMILAR SCOPE OF WORK ON 2007. ONCE PLANS ARE FOUND TO |
| | BE CODE COMPLIANT AND BEFORE ISSUANCE OF PERMIT THE |
| | PREVIOUS PERMIT #07100632PERMIT NEEDS TO BE VOIDED. |
| | PLEASE BE SURE LETTER IS ORIGINAL, COMPANY LETTER HEAD |
| | AND NOTARIZED CORRECTLY PER FS 117.05. |
| | |
| | 6) NOTE: PLEASE SEE 700.12F AS THE EMERGENCY AND EXIT |
| | LIGHTS SHALL BE CIRCUITED TO LOCAL BRANCH CIRCUIT. |
| | THERE IS A * NOTE* ONPLANS WHICH MENTIONS THIS |
| | HOWEVER THERE IS ALSO A CONTRADICTING NOTE #8 WHICH |
| | SPECIFICALLY STATES TO CONNECT THESE SAME LIGHTS TO AN |
| | *EMERGENCY CIRCUIT WITH A LOCK ON DEVICE*. |
| | THIS DOES NOT MEET THE MINIMUM REQUIRED BY CODE. PLEASE |
| | ADJUST PLANS. PLEASE ALSO SEE NEXT NOTE: |
| | |
| | 7) NOTE: PLANS ONLY INDICATE ONE EXIT SIGN AT ENTRANCE. |
| | PLEASE SEE NFPA-101 FOR MINIMUM FOR EXIT AND EMERGENCY |
| | LIGHTING REQUIRED. PLEASE SEE 7.8.1 AND 7.10 |
| | THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL. |
| | |
| | 8) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| | COORDINATE WITH THE SUBMITTED PANEL SCHEDULES. |
| | 408.4. |
| | FBC 106.3.5.1.2 |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |