Plan Review Notes
Plan Review Notes For Permit 08040069
Permit Number 08040069
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-09 09:03:36** DENIED REVIEW**
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON ELECTRICAL PLANS.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 PLEASE SEE COVER SHEET MENTIONS FLORIDA ENERGY CODE PER
 CHAPTER 11 AND 13. CHAPTER 11 OF THE FBC IS FOR
 ACCESSIBILITY/ ADA.
 FBC 106.1.2, 106.3.5, FS 553.73 FOR INFORMATION
 REQUIRED ON PLANS.
  
 2) NOTE: PLEASE SEE PLANS NEED TO COMPLY WITH FBC
 CHAPTER 13, 13-415.2, 13-415.2.ABC.1.1, .1. AND .1.3.
 PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS.THE LIGHTING CALCULATIONS SUBMITTED ARE
 NOT CODE COMPLIANT AND ARE NOT POSSIBLE AS SHOWN.
 FOR EXAMPLE: PLEASE SEE TABLE SHOWS 38-32W FIXTURES.
 HOW IS THIS POSSIBLE WHEN SEVERAL FIXTURES ARE 96VA OR
 MORE? PLEASE SEE FIXTURES A1, A1PP ETC.
 PLEASE SPECIFICALLY SEE SECTION 13-415.2.ABC.1.1 AS
 NOTED ABOVE FOR TRACK LIGHTING ALSO.
  
 ** THE EXAMPLE ABOVE IS ONE EXAMPLE AND IS IN NO WAY
 ALL ITEMS WHICH NEED TO BE ADDRESS WITH RESPECT TO
 LIGHTING PERFORMANCE CALCULATIONS AND IS NOT AN
 EXHAUSTED LIST.
  
 3) NOTE: PLEASE SEE 210.8B2 AS GFI/GFI PROTECTION IS
 REQUIRED FOR ALL 15/20AMP 120VRECEPTACLES.
 PLEASE LIST/SHOW ALL CIRCUITS.
  
 4) NOTE: PLEASE VERIFY SERVICE AS THE PANELS ARE
 SHOWING THESE AS 5-PHASE BASED ON PANELS SHOWN ON RISER
 DIAGRAM. THIS IS NOT POSSIBLE AND MUST BE SOME SORT OF
 MIS-PRINT.
 PLEASE ALSO CLARIFY OTHER DESIGNATIONS SHOWN ON THE
 PANELS ON RISER.
  
 5) NOTE: PLEASE KNOW THAT AN APPLICATION WAS MADE FOR
 SIMILAR SCOPE OF WORK ON 2007. ONCE PLANS ARE FOUND TO
 BE CODE COMPLIANT AND BEFORE ISSUANCE OF PERMIT THE
 PREVIOUS PERMIT #07100632PERMIT NEEDS TO BE VOIDED.
 PLEASE BE SURE LETTER IS ORIGINAL, COMPANY LETTER HEAD
 AND NOTARIZED CORRECTLY PER FS 117.05.
  
 6) NOTE: PLEASE SEE 700.12F AS THE EMERGENCY AND EXIT
 LIGHTS SHALL BE CIRCUITED TO LOCAL BRANCH CIRCUIT.
 THERE IS A * NOTE* ONPLANS WHICH MENTIONS THIS
 HOWEVER THERE IS ALSO A CONTRADICTING NOTE #8 WHICH
 SPECIFICALLY STATES TO CONNECT THESE SAME LIGHTS TO AN
 *EMERGENCY CIRCUIT WITH A LOCK ON DEVICE*.
 THIS DOES NOT MEET THE MINIMUM REQUIRED BY CODE. PLEASE
 ADJUST PLANS. PLEASE ALSO SEE NEXT NOTE:
  
 7) NOTE: PLANS ONLY INDICATE ONE EXIT SIGN AT ENTRANCE.
 PLEASE SEE NFPA-101 FOR MINIMUM FOR EXIT AND EMERGENCY
 LIGHTING REQUIRED. PLEASE SEE 7.8.1 AND 7.10
 THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL.
  
 8) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULES.
 408.4.
 FBC 106.3.5.1.2
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  