2008-04-22 09:29:38BUILDING PLAN REVIEW
 PERMIT: 08040069
 ADD: 1105 N DIXIE HWY
 CONT: VENTURA CONSTRUCTION CORP
 TEL: (561)937-1850
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS SHEET A0 APPLICABLE
 CODES
 INDICATES 2006 PLEASE UPDATE.
  
 1F) SHEET A0 APPLICABLE CODES THE FLORIDA ENERGY
 EFFICIENTY CODE IS CHAPTER 13 NOT 11, PLEASE CORRECT.
  
 1G) CHAPTER 11 IS THE FLORIDA ACCESSIBILITY CODE,
 PLEASE CORRECT.
  
 1H) SHEET A0 UNDER PROJECT SUMMARY OCCUPANCY
 CLASSIFICATION REFERENCES3051 PLEASE CORRECT.
  
 1I) SHEET A0 GENERAL NOTE 13 ALL INTRUSION PREVENTING
 DEVICES SHALL CONFORM TO CHAPTER 36 OF THE FBC, CHAPTER
 36 IS THE REFERENCE TO THE FIRE PREVENTION CODE, PLEASE
 EXPLAIN, ADDITIONAL INFORMATION REQUIED, 106.1.2.
  
 1J) SHEET A0 GENERAL NOTE 24 IMPERVIOUS MATERIALS AS
 PER SECTION 1408.2 (B) FBC, SECTION 1408.2 DEALS WITH
 THE HIGH VELOCITY HURRICANE ZONESASPHALT SHINGLES FOR
 DADE AND BROWARD COUNTIES, PLEASE CORRECT CODE
 SECTION.
  
 2) SHEET A0 PROJECT SUMMARY DECLARES THIS AS A TYPE IIA
 BUILDING AND WILL BE REVIEWED AS SUCH, THE MINIMUM
 BUILDING TYPE PER THE FBC WOULD BE 5B WITHOUT THE FIRE
 SPRINKLERS.
  
 3)PLANS INDICATE THIS BUILDING TO BE LOCATED ON LOT#
 9 BUT THE BUILDING APPEARS TO BE AS WIDE AS THE LOT.
 PLEASE PROVIDE A COPY OF A RECORDED UNITY OF TITLE OR
 SEE ZONING ON THE 5TH FLOOR
 FOR A COPY OF THE UNITY OF TITLE FORM AND RECORD IT AT
 THE CLERK OF THE COURT, UNIFYING LOTS 7, 9 & 11. UNITY
 OF TITLE. THE PROPOSED BUILDING STRUCTURE TRANSGRESSES
 LEGAL BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO
 FORM 'THE SITE'.A 'UNITY OF TITLE' SHALL BE RECORDED
 AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED
 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE. SEE ATTACHED SHEETS FROM PAPA.
  
 4)PLANS INDICATE THIS BUILDING IS FIRE SPRINKLERED,
 PLEASE PROVIDE THE LAY OUT PLAN. 106.3.5(4) MINIMUM
 PLAN REVIEW CRITERIA.
  
 5)NOTE AWNINGS REQUIRE A SEPERATE PERMIT.A LETTER
 FROM THE OWNER (NOT TENANT) IS TO ACCOMPANY ALLFABRIC
 OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC TO ACKNOWLEDGE
 THEIR RESPONSIBILITY TO HAVE THE AWNING COVER REMOVED
 PRIOR TO ANY WIND EVENT WITH PROJECTED WIND SPEEDS OF
 75 MPH OR GREATER. THE LETTER MUST BE SIGNED BY THE
 OWNER NOT TENANT.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH,
  
 6) SIGNS TO BE BY SEPERATE PERMIT.
  
 7)SHEET A-8DETAIL# 11 IS NOT DEPICTED ON ANY FLOOR
 PLAN LAYOUT, IS THIS THE NEW DECROTIVE SOFFIT THAT THE
 PERMIT APPLICATION IS INDICATED AS NEW WORK TO BE
 COMPLETED UNDER THIS PERMIT?
 THIS SECTION MAKES IT APPEAR THIS IS A NEW FEATURE, IF
 SO PLEASE PROVIDE WHAT TYPE OF MATERIALS THIS AREA WILL
 BE CONSTRUCTED WITH. NOTE TYPEIIA NON COMBUSTIBLE
 MATERIALS. PLEASE PROVIDE THE FOLLOWING WIND
 INFORMATION IF THIS IS A NEW FEATURE :
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 8) SHEET A-8 NOTE INDICATES USE OF PLYWOOD ON THE
 INTERIOR WALLS, PLEASE REVIEW 603 NONCOMBUSTIBLES IN
 TYPE IAND II BUILDINGS.
  
 9) DEPENDING ON THE LAST OCCUPANCY MAY REQUIRE IMPACT
 FEE REVIEW: BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.