| Date |
Text |
| 2008-04-04 16:03:19 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. NOTE: THE PLUMBING PERMIT BEING APPLIED FOR |
| | REFERENCES MASTER PERMIT NUMBER 08030319. PLEASE KNOW |
| | THAT THERE WAS NO PLUMBING PLAN REVIEW OR APPROVAL FOR |
| | THE PLUMBING BEING DEMOED ON MASTER PERMIT NUMBER |
| | 08030319. PLEASE KNOW THAT THIS PLUMBING REVIEW IS |
| | BEING DONE ON PLANS SUBMITTED FOR PERMIT NUMBER |
| | 08030319 AND THAT THE FOLLOWING ARE CONCERNS WITH THE |
| | PLUMBING DEMO. |
| | |
| | A} WHAT IS THE SQUARE FOOTAGE, USE AND OCCUPANCY LOAD |
| | FOR THE 1ST FLOOR? PER FBC PLUMBING TABLE 403.1 MINIMUM |
| | NUMBER OF REQUIRED PLUMBING FIXTURES. IT APPEARS THAT |
| | THIS IS A BUSSINESS. THE FOLLOWING ARE MINIMUM NUMBER |
| | OF PLUMBING FIXTURES REQUIRED FOR A BUSSINESS. WATER |
| | CLOSETS = 1 PER 25 FOR THE FIRST 50 AND 1 PER 50 FOR |
| | THE REMAINDER EXCEEDING 50. LAVATORIES = 1 PER 40 FOR |
| | THE FIRST 50 AND 1 PER 80 FOR THE REMAINDER EXCEEDING |
| | 50. DRINKING FOUNTAIN = 1 PER 100. IT ALSO APPEARS THE |
| | THAT REQUIRED DRINKING FOUNTAIN IS BEING DEMOED. PLEASE |
| | CLARIFY THESE ISSUES. |
| | |
| | B} IT APPEARS THAT THE BATHROOMS BEING DEMOED ARE MORE |
| | ADA ACCESSIBLE THAN THE EXISTING BATHROOMS. PER |
| | 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS. (1) |
| | GENERAL. ALTERATIONS TO EXISTING BUILDINGS AND |
| | FACILITIES SHALL COMPLY WITH THE FOLLOWING. (A) NO |
| | ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES OR HAS |
| | THE EFFECT OF DECREASING ACCESSIBILITY OR USABILITY OF |
| | A BUILDING OR FACILITY BELOW THE REQUIREMENTS FOR NEW |
| | CONSTRUCTION AT THE TIME OF ALTERATION. |
| | |
| | C} IS THE SANITARY PLUMBING DEMO OF THE FIRST FLOOR |
| | GOING TO AFFECT THE SANITARY PLUMBING TO THE UPPER |
| | FLOORS OF THIS BUILDING? PER FBC PLUMBING SECTION 701.1 |
| | SCOPE. |
| | |
| | D} PER FBC-2004 PLUMBING, SECTION 704.5 |
| | DEAD ENDS: IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | INSPECTION REQUIRED OF DEMO WORK PRIOR |
| | TO COVERING DEMO WORK WITH FINNISH |
| | WALLS, CIELINGS, OR POURED CONCRETE |
| | SLABS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |