| 2008-04-03 17:04:04 | 2004 FBC W/2007 REVISIONS | | | INSTALL 2 ACCORDION SHUTTERS ON SIX STORY CONDO | | | | | | DENIED BY BUILDING | | | | | | 1)THE DESIGN PRESSURE CALCULATIONS THAT WERE | | | SUBMITTED ARE FOR A MEAN ROOF HEIGHT OF 30 FEET OR | | | LESS. THE STRUCTURE IS FIVE TO SIX STORIES, THEREFORE | | | THEMEAN ROOF HEIGHT OF THE STRUCTURE IS ABOVE 30 | | | FEET. SUBMIT REVISED CALCULATIONS. IF THE MEAN ROOF | | | HEIGHT IS ABOVE 60 FEET SUBMIT SIGNED AND CALCULATIONS | | | FROM AN ENGINEER. FBC 106.1.2* CITY AMENDMENTS | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|