| Plan Review Notes For Permit 08040015 |
| Permit Number |
08040015 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-04-14 15:11:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.THE ENGINEERING WAS REMOVED FROM THE PERMIT | | | PACKAGE.ENGINEERING IS REQUIRED FOR BUILDINGS OVER | | | 60FEET USING ASCE7-02, SEE FBC1609.YOU ARE PROPOSING | | | TO USE A SYSTEM WITH A LIMITATION OF -120, BUT FBC | | | TABLE 1609.6.2.1(2) AND (4) WOULD REQUIRE A DESIGN | | | PRESSURE OF -144 FOR 60FEET, EXPOSURE C.THIS IS A 22 | | | STORY BUIDLING.PLEASE PROVIDE ENGINEERING AND SELECT | | | A SYSTEM WHICH COMPLIES WITH THE PRESSURES SPECIFIED BY | | | THE ENGINEER. |
|