| Plan Review Notes For Permit 08040011 |
| Permit Number |
08040011 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-09 10:22:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLANS PAGE M0.1 CODE COMPLIANCE REFERENCES 'THE | | | LATEST EDITION' OF THE CODE, THE CITY OF W.P.B. HAS NOT | | | ADOPTED THE 2007 CODE. PLEASE SHOW ON PLAN 2004 F.B.C. | | | | | | 2) PLANS PAGE M0.1 CODE COMPLIANCE REFERENCES PALM | | | BEACH COUNTY AMENDMENTS. AS THE PERMIT APPLIED FOR IS | | | IN THE CITY OF W.P.B. PLEASE CORRECT TO THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | | | | 3) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF | | | ALL PAGES IN THE PLANS, PER 2004 W.P.B AMEND. 106.1.3. | | | | | | 4) PAGE M1.1 SHOWS A 28X20 EXHAUST DUCT PENETRATING THE | | | WALL OF THE GENERATOR ROOM, AS 2002 NFPA 374.1.2.3 | | | REQUIRES ENGINE ROOMS TO BE RATED A FIRE DAMPER WILL BE | | | NEEDED PER 2004 FBC/M 607.5.1. PLEASE CORRECT. | | | | | | 5) PLEASE ADD A DETAIL TO THE PLANS SHOWING THE METHOD | | | OF INSTALLATION FOR FIRE DAMPERS, PER 2004 FBC/M | | | 607.8. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|