Plan Review Notes
Plan Review Notes For Permit 08040011
Permit Number 08040011
Review Stop M
Sequence Number 1
Notes
Date Text
2008-04-09 10:22:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE M0.1 CODE COMPLIANCE REFERENCES 'THE
 LATEST EDITION' OF THE CODE, THE CITY OF W.P.B. HAS NOT
 ADOPTED THE 2007 CODE. PLEASE SHOW ON PLAN 2004 F.B.C.
  
 2) PLANS PAGE M0.1 CODE COMPLIANCE REFERENCES PALM
 BEACH COUNTY AMENDMENTS. AS THE PERMIT APPLIED FOR IS
 IN THE CITY OF W.P.B. PLEASE CORRECT TO THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 3) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF
 ALL PAGES IN THE PLANS, PER 2004 W.P.B AMEND. 106.1.3.
  
 4) PAGE M1.1 SHOWS A 28X20 EXHAUST DUCT PENETRATING THE
 WALL OF THE GENERATOR ROOM, AS 2002 NFPA 374.1.2.3
 REQUIRES ENGINE ROOMS TO BE RATED A FIRE DAMPER WILL BE
 NEEDED PER 2004 FBC/M 607.5.1. PLEASE CORRECT.
  
 5) PLEASE ADD A DETAIL TO THE PLANS SHOWING THE METHOD
 OF INSTALLATION FOR FIRE DAMPERS, PER 2004 FBC/M
 607.8.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]