| Plan Review Notes For Permit 08030728 |
| Permit Number |
08030728 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2009-01-21 11:12:32 | STORM SHUTTERS ARE DENIED. | | | | | | THE REVISION TO CHANGE CHANGE FROM IMPACT TO NON-IMPACT | | | WINDOWS IS OK. HOWEVER, THE PRODUCT APPROVALS THAT WERE | | | SUBMITTED FOR THE STORM PANELS IS INCOMPLETE AND IS FOR | | | THE 2001 CODE VERSION. SUBMIT STORM PANEL PRODUCT | | | APPROVALS FOR THE 2004 FBC WITH INSTALLATION | | | INSTRUCTIONS. SPECIFY ON THE INSTALLATION INSTRUCTIONS | | | THE MOUNTING TYPE (IE. DIRECT MOUNT, H TRACK, ETC.), | | | THE FASTENER TYPE AND FASTENER SPACING THAT WILL BE | | | USED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|