| Plan Review Notes For Permit 08030728 |
| Permit Number |
08030728 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-25 14:36:30 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | | FBC CHAPTER 1AS AMENDED. | | | | | | INDICATE COMPLIANCE WITH THE FOLLOWING ON THE PLAN. | | | 1} 230.70 GENERAL. | | | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN | | | A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE | | | CONDUCTORS. | | | | | | 2} 225.32 LOCATION. | | | THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER | | | INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED | | | OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR | | | STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A | | | READILY ACCESSIBLE LOCATION NEAREST THE POINT OF | | | ENTRANCE OF THE CONDUCTOR | | | | | | 3} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) | | | OR BRANCH CIRCUIT(S) | | | (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S) | | | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A | | | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM | | | INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING | | | ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE | | | WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING | | | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) | | | REQUIRED IN 250.50 SHALL BE INSTALLED. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|