| 2008-04-28 17:14:26 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 3 ALTERATIONS TO DETACHED GARAGE |
| | |
| | DENIED BY BUILDING 2004 FBC 106.1.2* CITY AMENDMENTS. |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) A SIGNED, SEALED AND DATED COPY OF THE SOIL REPORT |
| | IS REQUIRED. SEE FS 471. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R SECTION 704 INSPECTION |
| | FOR TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR |
| | TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL |
| | COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A |
| | BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| | |
| | 4) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| | GRADE . |
| | CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| | ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| | ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| | VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| | ELSEWHERE. |
| | |
| | 5)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST |
| | DECAY AND TERMITES. CONDENSATE LINES AND ROOF |
| | DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 MM) |
| | AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY |
| | UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS. |
| | GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS |
| | WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL |
| | PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF |
| | ABOVE ANOTHER ROOF. |
| | |
| | 6)SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / |
| | 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | |
| | 7) THE OPENING PRESSURES FOR THE EXTERIOR DOORS LOCATED |
| | IN WALL ZONE 5 ARE TOO LOW. PLEASE REVISE. SEE TABLE R |
| | 301.2(2). |
| | |
| | 8) THE WALL SECTIONS SPECIFY R-19 INSULATION IN THE |
| | EXTERIOR WALLS. THE WALLS ARE SPECIFIED AS 2 X 4 WHICH |
| | CAN ONLY ACCOMODATE R-11 INSULATION. PLEASE REVISE. |
| | |
| | 9) TRUSS NOTE (9) ON SHEET A4 NEEDS TO BE REVISED TO |
| | COMPLY WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO |
| | 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL PANEL |
| | SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH 8D |
| | RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND 6 |
| | INCHES ON CENTER AT INTERMEDIATE FRAMING. WHERE ROOF |
| | FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G < 0.49 IS |
| | USED, SPACING OF RING-SHANK FASTENERS SHALL BE 4 INCHES |
| | ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR GREATER |
| | DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1 |
| | . |
| | |
| | 10) ON SHEET A4 MASONRY NOTES 5 AND 6 SPECIFY THE WRONG |
| | EDITIONS OF ACI 530, ASCE5, ASCE6, TMS402 AND TMS602. |
| | THE 2002 EDITION OF THESE STANDARDS ARE REFERENCED IN |
| | THE 2004 FBC. SEE CHAPTER 43 OF THE 2004 FBC |
| | RESIDENTIAL. |
| | |
| | 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR WINDOWS, |
| | DOORS, OVERHEAD GARAGE DOORS, ROOF COVERING, CONNECTORS |
| | AND STORM PANELS AS REQUIRED BY DCA RULE 9B-72. |
| | |
| | 12) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13) NOTE: THE FLOOR PLAN SPECIFIES AN EGRESS WINDOW AND |
| | A TEMPERED GLASS WINDOW. BASED ON THE PLANS THAT WERE |
| | SUBMITTED, THESE WINDOWS ARE NOT REQUIRED TO BE EITHER. |
| | |
| | |