| 2008-08-07 16:55:41 | |
| | **DENIEDREVIEW** |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL ITEMS REVISED ON PLANS |
| | WHICH WERE NOT PART OF PREVIOUS COMMENTS NOR WAS IT |
| | BROUGHT UP IN MEETING PREVIOUSLY HELD BEFORE PLANS WERE |
| | RESUBMITTED. IT IS UNCLEAR WHY THESE ITEMS WERE |
| | REVISED. |
| | THE PREVIOUS REVIEW NOTES DID HAVE COMMENTS FOR THE |
| | NEED OF REVISING LOAD CALCULATIONS WHICH WERE NOW DONE |
| | HOWEVER THESE HAVE NOW CHANGED WHICH WOULD REQUIRE THE |
| | EXISTING MAIN TO BE UPGRADED. |
| | THE FOLLOWING ITEMS ARE NOW NOTED. |
| | |
| | |
| | 1) NOTE:THE FOLLOWING ARE EXAMPLES: |
| | PLEASE SEE THE FEEDERS SCHEDULE HAS NOW BEEN REVISED. |
| | PANEL *B* IS A 200AMP MCB PANEL NOW REVISED WITH TAPPED |
| | CONDUCTORS SHOWN AS 500MCM. THE 500MCM WILL NOT FIT |
| | INTO A 200AMP BREAKER. |
| | PLEASE SEE PANEL SCHEDULE FOR LA. THIS PANEL HAS NOW |
| | BEEN REVISED TO A 200AMP MCB WHICH IS OK. |
| | PLEASE SEE THE BREAKER IN PANEL *LB* WHICH IS SHOWING A |
| | 3-POLE 60AMP BREAKER WITH 1/0 FEEDERS. THE 1/0 FEEDERS |
| | WILL NOT FIT UNDER A LUG OF A 60AMP BREAKER. IN ANY |
| | CASE PLEASE LOOK AT LOAD CALCULATIONS. THE LOAD NOW |
| | SHOWN FOR PANEL *LP* IS SHOWN AT 163AMPS YET THE |
| | BREAKER AS NOTED IS ONLY 60AMPS AND THE FEEDERS AS 1/0 |
| | ARE ONLY RATED FOR 150AMPS. |
| | PLEASE SEE THE LOAD CALCULATIONS AS THE SERVICE LOAD IS |
| | NOW SHOWN AT 455AMPS ON A 400AMP MAIN. |
| | PLEASE SEE THE LOAD SHOWN ON PANEL *LB* FOR PANEL *LP*. |
| | THE LOAD ON SHEET E-4 FOR PANEL LP IS NOT THE SAME AS |
| | LOAD ON LB. |
| | ETC. |
| | 220,240.4,310.16,,110.3 |
| | NEITHER OF THESE TWO LOADS ARE THE SAME AS THE LOAD |
| | CALCULATIONS ON SHEET E-5. |
| | PLEASE CALL TO SET UP A MEETING AS SOON AS POSSIBLE TO |
| | GO OVER PLANS. |
| | PLACED CALLS TO ELECTRICAL CONTRACTOR, ARCHITECT AND |
| | EXPEDITOR. |
| | SPOKE TO CONTRACTOR AND THEY WERE NOT AWARE OF |
| | CHANGES. |
| | SPOKE WITH ARCHITECT AND A MEETING IS TO BE SET. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |