Date Text
2008-08-07 16:55:41 
 **DENIEDREVIEW**
  
 ** PLEASE SEE THERE ARE SEVERAL ITEMS REVISED ON PLANS
 WHICH WERE NOT PART OF PREVIOUS COMMENTS NOR WAS IT
 BROUGHT UP IN MEETING PREVIOUSLY HELD BEFORE PLANS WERE
 RESUBMITTED. IT IS UNCLEAR WHY THESE ITEMS WERE
 REVISED.
 THE PREVIOUS REVIEW NOTES DID HAVE COMMENTS FOR THE
 NEED OF REVISING LOAD CALCULATIONS WHICH WERE NOW DONE
 HOWEVER THESE HAVE NOW CHANGED WHICH WOULD REQUIRE THE
 EXISTING MAIN TO BE UPGRADED.
 THE FOLLOWING ITEMS ARE NOW NOTED.
  
  
 1) NOTE:THE FOLLOWING ARE EXAMPLES:
 PLEASE SEE THE FEEDERS SCHEDULE HAS NOW BEEN REVISED.
 PANEL *B* IS A 200AMP MCB PANEL NOW REVISED WITH TAPPED
 CONDUCTORS SHOWN AS 500MCM. THE 500MCM WILL NOT FIT
 INTO A 200AMP BREAKER.
 PLEASE SEE PANEL SCHEDULE FOR LA. THIS PANEL HAS NOW
 BEEN REVISED TO A 200AMP MCB WHICH IS OK.
 PLEASE SEE THE BREAKER IN PANEL *LB* WHICH IS SHOWING A
 3-POLE 60AMP BREAKER WITH 1/0 FEEDERS. THE 1/0 FEEDERS
 WILL NOT FIT UNDER A LUG OF A 60AMP BREAKER. IN ANY
 CASE PLEASE LOOK AT LOAD CALCULATIONS. THE LOAD NOW
 SHOWN FOR PANEL *LP* IS SHOWN AT 163AMPS YET THE
 BREAKER AS NOTED IS ONLY 60AMPS AND THE FEEDERS AS 1/0
 ARE ONLY RATED FOR 150AMPS.
 PLEASE SEE THE LOAD CALCULATIONS AS THE SERVICE LOAD IS
 NOW SHOWN AT 455AMPS ON A 400AMP MAIN.
 PLEASE SEE THE LOAD SHOWN ON PANEL *LB* FOR PANEL *LP*.
 THE LOAD ON SHEET E-4 FOR PANEL LP IS NOT THE SAME AS
 LOAD ON LB.
 ETC.
 220,240.4,310.16,,110.3
 NEITHER OF THESE TWO LOADS ARE THE SAME AS THE LOAD
 CALCULATIONS ON SHEET E-5.
 PLEASE CALL TO SET UP A MEETING AS SOON AS POSSIBLE TO
 GO OVER PLANS.
 PLACED CALLS TO ELECTRICAL CONTRACTOR, ARCHITECT AND
 EXPEDITOR.
 SPOKE TO CONTRACTOR AND THEY WERE NOT AWARE OF
 CHANGES.
 SPOKE WITH ARCHITECT AND A MEETING IS TO BE SET.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  