Plan Review Notes
Plan Review Notes For Permit 08030723
Permit Number 08030723
Review Stop P
Sequence Number 2
Notes
Date Text
2008-06-05 10:10:36DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-3 DETAIL D-1 INDICATES THE W/C'S TO BE 1'8"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. PER FIG
 11-28 THE W/C'S SHALL BE 1'6" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. PLEASE SHOW CORRECT
 DIMENSION TO THE CENTERLINE OF THE W/C'S. ****RESPONSE
 FROM ENGINEER STATES: "PLEASE REFER TO RESPONSE BY
 "ARCHITECT OF RECORD". NO RESPONSE FROM ARCHITECT OF
 RECORD. COMMENT NOT ADDRESSED.
  
 2. SHT A-3 DETAIL D-2 PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ****RESPONSE FROM ENGINEER STATES: "PLEASE REFER TO
 RESPONSE BY "ARCHITECT OF RECORD". NO RESPONSE FROM
 ARCHITECT OF RECORD. COMMENT NOT ADDRESSED.
  
 3. OK
  
 ***********NEW COMMENTS**********
 NEW SHEETS SUBMITTED
  
 1B. SHT 90-038 SURVEY NOT SEALED OR DATED AS REQUIRED
 IN FS 472.025(1)
  
 2B. SHTS SP-1, A-1, A-2, A-3 & A-4 ARE NOT SIGNED,
 SEALED & DATED AS REQUIRED. FAC 61G1-16.003,
 61G16-004(5) AND FS 481.2055.
  
 3B. SHTS PL 1.00, PL 2.00 & PL 3.00 REQUIRES THE
 BUSINESS LICENSE, (CERTIFICATE OF AUTHORIZATION), AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT IN
 THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2)(6) &
 FS 481.306, 481.319.
  
 4B. LAST NEW SHEET HAS NO TITLE BLOCK AND IS NOT
 SIGNED, SEALED, DATED. IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED UNDER THE LAWS
 OF THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE
 AS PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART
 I, OR ENGINEERING AS PROVIDED FOR IN CHAPTER 471,
 FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS AS
 REQUIRED BY FLORIDA STATUTES. SECTION 106.1.
  
 5B. SEE ATTACHED SHEET CONCERNING FLORIDA STATUTE
 553.80(2)(B) AND THE DESIGN PROFESSIONALS. THIS IS
 GIVEN AS NOTICE ONLY AT THIS TIME.
  
 6B. ONE SET OF PLANS WILL BE RETAINED BY THIS OFFICE
 FOR POSSIBLE REVIEW BY THE ARCHITECTURAL, ENGINEER &
 SURVEY BOARDS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]